Configure a ControlNet Module
Chapter 3
7.
To change the network properties from default settings to those that best
fit your network, from the Network menu, choose Properties.
8.
On the Network Parameters tab, configure the network parameters as
described in the table below.
Parameter
Description
Network Update Time
The smallest user-configurable repetitive time cycle in milliseconds at
which data can be sent on a ControlNet link.
Max Scheduled Address
The node with the highest network address that can use scheduled
time on a ControlNet link. I/O data is transferred during scheduled time.
RSNetWorx for ControlNet software sets this value. We recommend
that you do not change it.
Max Unscheduled Address
The node with the highest network address that can use unscheduled
time on a ControlNet link. Messaging data is transferred during
unscheduled time.
Nodes set at addresses higher than the maximum unscheduled node do
not communicate on the network. For example, they will not display in
RSLinx software.
Media Redundancy
Designates if the network uses media redundancy on any of the
network communication modules.
Network Name
A user-defined name for the network.
Rockwell Automation Publication CNET-
UM001E-EN-P - June 2016
51