3–8
Installing the KFC15/KFCD15 Module
Publication 17706.5.20 - June 1997
!
ATTENTION: If the KFC15/KFCD15 module is
connected to a cable system that does not support
redundant media, the tap dropline should be connected
to the BNC connector labeled channel A. The channel
B connector should be unused. If the cable system is
redundant, the KFC15/KFCD15 module should be
connected such that all devices on the network use the
same cable for the same channel. The channel A
connector on all products should be connected to the
same cable. The same applies for the channel B
connectors.
To connect the KFC15/KFCD15 module to the tap do the following:
1. If the KFC15/KFCD15 module is not the last device in the
segment:
•
Connect the tap to the coaxial trunkline.
•
Connect the dropline BNC to the channel A BNC of the
KFC15/KFCD15 module.
2. If the KFC15/KFCD15 module is the last device in the segment,
install a terminator at the end of the cable segment, then follow
the instructions in step 1.
3. If using redundant media, repeat either step 1 or step 2 for
channel B of the KFC15/KFCD15 module.