Publication 1756-UM001E-EN-P - August 2002
17-14
Communicate with Another Controller Over a DH+
™
Network
Enter a Message
A.
Enter a MSG instruction and associated input instruction (s).
42424
B.
In the MSG instruction, type a name for the message control tag
and press the
Enter
key.
C.
In the MSG instruction, right-click the message control tag and
select
New
tag_name.
(In older revisions of the software, the
menu option is
Create
tag_name.
)
D.
From the
Scope
list, select
name_of_controller
(controller)
,
and click
OK
.
42424
E.
Enter
message.
EN.
where:
message
is the message control tag from step B.
F.
If your message is to a PLC-5
®
or SLC 500
™
controller
and
it
reads or writes integers (not REALs), use a buffer of INTs in the
message.
•
ControlLogix controllers execute more efficiently and use less
memory when working with 32-bit integers (DINTs). Use the
DINT data type for integers whenever possible.
•
PLC-5 and SLC 500 controllers require 16-bit integers.
•
Use an INT buffer in the message and move the data into or
out of the buffer as required.
e
e
e
e
e
e
condition
/
?
EN
DN
ER
Message
Message Control
? ...
MSG
e
e
e
e
e
condition
/
?
EN
DN
ER
Type - Unconfigured
Message Control
message ...
MSG
E.
Summary of Contents for controllogix 1756-L63
Page 1: ...ControlLogix System 1756 L1 L1Mx L55Mxx L63 User Manual Allen Bradley HMIs...
Page 4: ...Publication 1756 UM001E EN P August 2002 Summary of Changes 2 Notes...
Page 16: ...Publication 1756 UM001E EN P August 2002 Table of Contents x...
Page 268: ...Publication 1756 UM001E EN P August 2002 15 4 Monitor Connections Notes...
Page 276: ...Publication 1756 UM001E EN P August 2002 16 8 Communicate with a DeviceNet Device Notes...
Page 402: ...Publication 1756 UM001E EN P August 2002 24 22 Program Motion Control Notes...
Page 408: ...Publication 1756 UM001E EN P August 2002 25 6 Maintain the 1756 BA1 Battery Notes...
Page 418: ...Publication 1756 UM001E EN P August 2002 B 2 Estimate Execution Time...
Page 420: ...Publication 1756 UM001E EN P August 2002 C 2 Estimate Memory Use...
Page 422: ...Publication 1756 UM001E EN P August 2002 D 2 Determine When Data Is Updated Notes...
Page 424: ...Publication 1756 UM001E EN P August 2002 E 2 Reconfigure an I O module Notes...
Page 428: ...Publication 1756 UM001E EN P August 2002 4 Index...
Page 429: ...Publication 1756 UM001E EN P August 2002 Index 5 Allen Bradley HMIs...
Page 430: ...Publication 1756 UM001E EN P August 2002 6 Index...
Page 435: ...ControlLogix System User Manual Allen Bradley HMIs...