Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
79
Configure Switch Features
Chapter 3
Alarms
Alarms vary by switch model.
Switch
Alarm Description
Stratix® 5400 switch
The switch lets you connect two alarm inputs from external devices, such as a door or temperature gauge, to the alarm input port on the
front panel of the switch.
An over- or under-temperature alarm or a port not forwarding condition automatically triggers the default output. You can configure the
output alarm relay as either normally energized or de-energized.
Stratix 5410 switch
The switch provides the following external alarms:
•
Four alarm inputs to sense whether the alarm setting is open or closed. The alarm input is a dry-contact alarm port. You can connect up to
four alarm inputs from devices, such as a door, a temperature gauge, or a fire alarm to the alarm port. An alarm generates a system
message and turns on an alarm status indicator.
•
One alarm output that you can configure as a minor or major alarm. Output alarms often control an external
alarm, such as a bell or a
light. To connect an external alarm device to the relay, you connect two relay contact wires to complete the electrical circuit.
The front panel alarm port uses an RJ45 connector.
Stratix 5700 switch
The switch lets you connect two alarm inputs from external devices, such as a door or temperature gauge, to the alarm input port on the
front panel of the switch.
An over- or under-temperature alarm or a port not forwarding condition automatically triggers the default output. You can configure the
output alarm relay as either normally energized or de-energized.
ArmorStratix™ 5700 switch
The switch provides the following external alarms:
•
One input alarm relay circuit to sense whether the alarm input is open or closed relative to the alarm input reference pin.
•
One output alarm relay circuit with one Form C (single-pole, double-throw) relay with one normally open (N.O.) and one normally closed
(N.C.) contact. You can configure the output alarm as either normally energized or normally de-energized.
Stratix 8000/8300 switch
The switches provide the following on the front panel:
•
Major alarm relay—When closed, the major alarm relay indicates a dual-mode power supply or primary temperature alarm.
•
Minor alarm relay—When closed, the minor alarm relay indicates these alarm states:
–
Link fault
–
Port not forwarding
–
Port not operating
–
Frame Check Sequence (FCS) bit error rate
Summary of Contents for armorstratix 5700
Page 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Page 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Page 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Page 457: ......