Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
135
Bulletin 290E/291E/294E Programmable Parameters
Chapter
4
Speed Control Group
SpeedReference
Sets the source of the speed reference:
0 = Logix (Network or DeviceLogix)
1 = InternalFreq
Parameter Number
33
Related Parameters
1, 2, 36, 37, 72
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
—
Minimum Value
0
Maximum Value
2
Default Value
0
MinimumFreq
Sets the lowest frequency the drive will
output continuously.
Parameter Number
34
Related Parameter
1, 2, 35
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
x.x Hz
Minimum Value
0.0
Maximum Value
400.0
Default Value
0.0
MaximumFreq
Sets the highest frequency the drive will
output.
Parameter Number
35
Related Parameter
1, 2, 34, 35, 139
Access Rule
GET/SET
Data Type
UINT
Group
Speed Control
Units
Hz
Minimum Value
0.0
Maximum Value
400
Default Value
60
Stop drive before changing this
parameter.