Publication 1792D-IN017B-EN-P - September 2000

Installation Instructions

ArmorBlock MaXum 4 Input Module 
Series B

(Cat. No. 1792D-4BV0D)

This ArmorBlock MaXum

 I/O module (Cat. No. 1792D-4BV0D) is a 

stand-alone 24V dc I/O product which communicates via a 
DeviceNet

 network. The sealed housing of this module requires no 

enclosure. 

This model has 4 inputs. Inputs are 24V dc automatically configured 
for PNP (sourcing) or NPN (sinking) devices. Diagnostic features 
included are short circuit and open wire detection reported to the 
point level. Local logic control has been added to the Series B version 
of this product.

 41455

Summary of Contents for ArmorBlock MaXum 4

Page 1: ...4V dc I O product which communicates via a DeviceNet network The sealed housing of this module requires no enclosure This model has 4 inputs Inputs are 24V dc automatically configured for PNP sourcing or NPN sinking devices Diagnostic features included are short circuit and open wire detection reported to the point level Local logic control has been added to the Series B version of this product 41...

Page 2: ...ndards in whole or in part documented in a technical construction file EN 50081 2 EMC Generic Emission Standard Part 2 Industrial Environment EN 50082 2 EMC Generic Immunity Standard Part 2 Industrial Environment This product is intended for use in an industrial environment Low Voltage Directive This product is tested to meet Council Directive 73 23 EEC Low Voltage by applying the safety requireme...

Page 3: ...ol Each module is shipped set for node address 63 The switches are located on the underside of the module The two switches are MSD most significant digit LSD least significant digit To reset the node address use a small blade screwdriver to rotate the switches Line up the small black dot on the switch with the number setting you wish to use The rotary switches are read at module power up only Sett...

Page 4: ...media installation 1792D CB12 for 12mm drop cable installation 1792D CB18 for round media trunk connection or other optional cable base assembly IMPORTANT The cable base should already be installed See publication 1792D IN009B EN P for information on installing the cable base NODE ADDRESS 00 63 PGM LSD MSD 0 1 2 3 4 5 8 9 7 6 0 1 2 3 4 5 8 9 7 6 Bottom View of Module Example Node Address is set at...

Page 5: ...n the screws with a torque of 8 inch pounds to secure the module to the base Note Dimensions change according to the cable base and module combination used IMPORTANT Proper alignment of the screws is necessary to complete the connections between the module contacts and the cable contacts Align the screws to properly assemble the module to the base 41517 2 7 68 6 1 9 48 26 Cable Base 1792D CBFM is ...

Page 6: ...ted to the input connections require Class 2 power to operate the DeviceNet connections of this equipment must be powered by a Class 2 source ATTENTION Make sure all connectors and caps are securely tightened to properly seal the connections against leaks and maintain IP67 requirements For maximum noise immunity input and output cable return wires must be properly terminated When inputs and output...

Page 7: ... Cable Planning and Installation Manual Communicate With Your ArmorBlock MaXum Module This ArmorBlock module s I O is exchanged with the master through a poll change of state or cyclic connection The module produces or consumes data as follows Cyclic allows configuration of the block as an I O client The block will produce and consume its I O cyclically at the rate configured Type of I O Connectio...

Page 8: ...n to increase network functionality and throughput Visit our web site at http www ab com networks for producer consumer technology information and updates Bit 07 06 05 04 03 02 01 00 Produces 0 ISC D ISC C ISC B ISC A I3 I2 I1 I0 Produces 1 RSVD RSVD RSVD RSVD OW D OW C OW B OW A Where OW Off Wire I Input ISC Input Short Circuit in Sensor Source Voltage RSVD Reserved Byte Bit Description Produces ...

Page 9: ...to bauding Flashing Green Off On line but not connected Solid Green On line link OK connected Flashing Red Recoverable fault module configuration error I O connection fault one or more I O connections in the timed out state Solid Red Unrecoverable fault Communication failure duplicate node address present or incorrect baud rate Green to Red to Off At powerup only LED test 41461 Connector A Connect...

Page 10: ...cal Data publication 1792 TD001B EN P Logic Status Indicators State Status Off Logic is disabled Solid Green Logic is enabled Flashing Green Local forces are applied and local logic is enabled I O Status Indicators Function Module Status Indicator Point Indicator Condition Inputs Green Green Module status blink red Module status blink red None Yellow Red Blink Red No valid input Valid input Short ...

Page 11: ...ltage Current Refer to the graphs in the Overview section of the ArmorBlock I O Family Technical Data pub no 1792 TD001B EN P 25V dc max 150mA max no sensors 11V dc min up to 8A 4 sensors 50mA per sensor Dimensions assembled to base inches millimeters 1 9H x 2 7w x 4 72D 48 26 H x 68 6 W x 120 D Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating ...

Page 12: ...rmine the overall temperature code of the system Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation WARNING EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous Do not disconnect connections to this equipment unless power has been removed or the ar...

Page 13: ...isons d équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING When used in a Class I Division 2 hazardous location this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes AVERTISSEMENT RISQUE D EXPLOSION Couper le courant ou s assurer que l environnem...

Page 14: ...lease contact the ODVA website http www odva org for listing of products tested by ODVA independent test labs for further details AVERTISSEMENT Utiliser des fils d alimentation qui conviennent à une température de 30 C au dessus de la température ambiante AVERTISSEMENT Pour une utilisation en environnement de classe i division 2 dangereux cet equipement doit etre monte dans un boitier avec un cabl...

Page 15: ...ArmorBlock MaXum 4 Input Module Series B 15 Publication 1792D IN017B EN P September 2000 Notes ...

Page 16: ...nternational Corporation Printed in USA ArmorBlock ArmorBlock MaXum and KwikLink are trademarks of Rockwell Automation RSNetWorx for DeviceNet is a trademark of Rockwell Software Inc DeviceNetManager is a trademark of Rockwell Automation Allen Bradley Inc DeviceNet is a trademark of Open DeviceNet Vendor Association ODVA ...