Installation
Chapter 2
Hazardous Locations
This equipment is suitable for these location categories.
Computer Model
Cat. Nos.
Region
Rating
Temperature Range
Non-display
(1)
6181X-NPXPDC,
6181X-NPW7DC
United States
Class I Division 2, Groups A, B, C, D T4
-20 °C < T
a
< 70 °C
(-4 °F < T
a
< 158 °F)
Class I Zone 2, IIC, T4
Canada
Class I Division 2, Groups A, B, C, D T4
Class I Zone 2, IIC, T4
Europe
ATEX II 3 GD, Ex nA IIC Gc, Ex tc IIIC Dc
Global/IECEx
Ex nA IIC Gc, Ex tc IIIC Dc
Display (12 in.)
(2)
6181X-12TPXPDC,
6181X-12TPW7DC
United States
Class I Division 2, Groups A, B, C, D T4
-20 °C < Ta < 55 °C
(-4 °F < Ta < 131 °F) (display side)
-20 °C < Ta < 70 °C
(-4 °F < Ta < 158 °F) (backside)
(3)
Class I Zone 2, IIC, T4
Canada
Class I Division 2, Groups A, B, C, D T4
Class I Zone 2, IIC, T4
Europe
ATEX II 3 GD, Ex nA nC IIC T4 Gc,
Ex tc IIIC T135° Dc
Global/IECEx
Ex nA nC IIC T4 Gc, Ex tc IIIC T135 °C Dc
(1) The following applies only to non-display models in ATEX and IECEx applications:
Schedule of Limitations (U)
•
For EPL Gc, the industrial computer shall be completely installed in an enclosure providing a minimum degree of protection of IP54 and used in an area of not more
than pollution degree 2. For EPL Dc, a minimum protection of IP6x is required. In addition, the enclosure shall also meet the applicable enclosure requirements of
EN/IEC 60079-0: 2012/2011, EN/IEC 60079-15: 2010 and EN/IEC 60079-31: 2014/2013.
•
The USB ports shall not be used unless the area is known to be non-hazardous. All other ports or connections shall not be disconnected unless the area is known to
be non-hazardous.
(2) The following applies only to display models in ATEX and IECEx applications:
Special Conditions for Safe Use (X)
•
For EPL Gc, the industrial computer shall be installed in the wall of an enclosure providing a minimum degree of protection of IP54 and used in an area of not more
than pollution degree 2. For EPL Dc, a minimum protection of IP6x is required. In addition, the enclosure shall also meet the applicable enclosure requirements of
EN/IEC 60079-0: 2012/2011, EN/IEC 60079-15: 2010 and EN/IEC 60079-31: 2014/2013.
•
The service temperature of the enclosure in which a 6181X-12T display model is installed shall not exceed 70 °C (158 °F) when the user considers heating from all
other heat sources within the enclosure.
•
The USB ports shall not be used unless the area is known to be non-hazardous. All other ports or connections shall not be disconnected unless the area is known to
be non-hazardous.
(3)
The entire non-display computer and the backside of the display computer are required to be mounted in a restricted access location.
Summary of Contents for 6181X-12TPW7DC
Page 4: ...4 Rockwell Automation Publication 6181X UM001C EN P July 2015 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication 6181X UM001C EN P July 2015 Table of Contents Notes...
Page 34: ...34 Rockwell Automation Publication 6181X UM001C EN P July 2015 Chapter 3 Operation Notes...
Page 67: ......