Chapter 2
Installation
Installation Precautions
Read and follow these precautions before you install the computer.
Environment and Enclosure Information
European Union Directive
This computer meets the European Union Directive requirements when installed
within the European Union or EEA regions and have the CE mark. A copy of the
declaration of the conformity is available at
http://www.rockwellautomation/
.
To comply with EN 55022 and EN 55024, use the following for cable types.
ATTENTION:
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC 60664-1),
at altitudes up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR 22. Without appropriate precautions, there can be potential difficulties
with electromagnetic compatibility in other environments due to conducted as
well as radiated disturbance.
This equipment is supplied as an open type equipment. To meet some regulatory
requirements, the computer must be mounted in an enclosure that is suitably
designed for environmental conditions that can be present and appropriately
designed to help prevent personal injury resulting from accessibility to live parts.
The interior of the enclosure must be accessible only by using a tool.
All 6181X-12 display computers are shipped with a gasketed bezel to meet
specified NEMA, UL Type, and IEC ratings only when mounted in a panel or
enclosure with an equivalent rating.
In addition to this publication, see the following:
•
Industrial Automation Wiring and Grounding Guidelines, publication
,
for additional installation requirements
•
NEMA Standard 250, UL 50, and IEC 60529, as applicable, for explanations of
the degrees of protection that are provided by enclosures
ATTENTION:
To comply with EN 55022 and EN 55024, all I/O cables must be less
than 30 m (98.42 ft) and used only indoors. These cables cannot exit the building
at any point and cannot directly connect to cables outside the building.
Cable Type
Required Attribute
Cable Type
Required Attribute
LAN
Shielded or unshielded
DP
Shielded
USB
Shielded
VGA
Shielded
Serial RS-232
Shielded
DC power
Unshielded
DVI
Shielded