Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
273
Appendix
C
Application and Wiring Examples for Safety
Modules
This appendix provides example wiring diagrams for the Compact 5000™ I/O
safety modules that can be used in functional safety applications.
The wiring configuration affects the safety application level to which a
Compact 5000 I/O safety module is suitable.
Before You Begin
Before you wire your module, remember the following:
A system can have multiple SA power buses. You use 5069-FPD field potential
distributors to establish a new SA power bus. SA power buses are isolated from
each other.
The SA Power to adjacent SA Power electrical isolation that the 5069-FPD
field potential distributor provides has a rating of 240V AC (continuous)
reinforced insulation type.
Topic
Page
5069-IB8S or 5069-IB8SK Module Wiring Diagrams
5069-OBV8S and 5069-OBV8SK Module Wiring Diagrams
IMPORTANT
This section shows example wiring diagrams on the 5069-IB8S safety input
module and the 5069-OBV8S safety output module.
The same diagrams also apply when you use the 5069-IB8SK safety input
module and the 5069-OBV8SK safety output module, respectively.