Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
117
Output Module Features
Chapter 4
Other Conditions That Can Trigger the Short Circuit Diagnostic on
the 5069-OBV8S or 5069-OBV8SK Module
Table 32
describes conditions that can trigger the Short Circuit diagnostic.
When the conditions that trigger the diagnostics as described in
Table 32
are
corrected, the results are the same as described in
Table 32 - Conditions That Trigger Short Circuit Diagnostic
Conditions
Output Behavior
Tag and Diagnostic Combinations
I/O Status Indicator State
• Output Mode - Sourcing
• Point Operation Type - Single
• Point Mode - Safety Pulse Test
• O.Ptxx.Data tag = 1
• Output point is
shorted to 24V DC.
• Faults
• Turns off
• I.Ptxx.ShortCircuit tag = 1
• Short Circuit diagnostic = 1
• I.Ptxx.Fault tag = 1
Or
• I.Ptxx.Fault tag = 1
• Internal Fault diagnostic = 1
IMPORTANT
: The tag and diagnostic combinations that are
described occur on the faulted output point and all of its
associated group points.
The I/O status indicator for
the faulted output point
turns off.
The following conditions exist on a pair of module
outputs:
• Output Mode - Sourcing
• Point Operation Type - Dual
• Point Mode - Safety Pulse Test
• O.Ptxx.Data tag = 1 (Either output point in the pair)
• Output point is
shorted to 24V DC (Either output
point in the pair)
.
• Faults
• Turns off
• I.Ptxx.ShortCircuit tag = 1
• I.Ptxx.Fault tag = 1
• Short Circuit diagnostic = 1
• Internal Fault diagnostic = 1
Or
• I.Ptxx.Fault tag = 1
• Internal Fault diagnostic = 1
IMPORTANT
: The tag and diagnostic combinations that are
described occur on the faulted output point and all of its
associated group points.
The following conditions exist on a pair of module
outputs:
• Output Mode - Sourcing
• Point Operation Type - Dual
• O.Ptxx.Data tag = 1 (Both output points in the pair)
• Output points are
shorted to each other.
• Faults
• Turns off
• I.Ptxx.ShortCircuit tag = 1 (Both output points in the
pair)
• Short Circuit diagnostic = 1 (Both output points in the
pair)
• I.Ptxx.Fault tag = 1
Or
• I.Ptxx.Fault tag = 1 (Faulted output point and all of its
associated group points)
• Internal Fault diagnostic = 1 (Faulted output point and all
of its associated group points