Terminal Connections
Chapter 6
DH+ Network Connections
Use a Belden 9463 twin-axial or equivalent cable, catalog number 1770-CD, to
connect a terminal to a DH+ link.
You can connect a DH+ link in two ways:
• Trunk line/drop line
- from the drop line to the connector screw
terminals on the DH+ connectors of the processor.
• Daisy chain
- to the connector screw terminals on the DH+ connectors
on the processor.
Follow these guidelines when installing DH+ communication links:
•
Do not exceed these cable lengths:
–
Trunk line-cable length: 3048 m (10,000 ft)
–
Drop-cable length: 30.4 m (100 ft)
The maximum cable length is determined by the baud rate.
•
Do not connect more than 64 stations on a single DH+ link.
Figure 23 - Terminal Connection to DH+ Link
700 TO 1500 Terminal with
DH-485/DH+ Communication Module
•
82
Ω
terminating resistor for
230.4 Kbps
•
150
Ω
terminating resistor for
57.6 Kbps and 115.2 Kbps
To Controller
Terminating Resistor
DH+ Port on Communication Module
Clear 1
Shield SH 2
Blue 3
Belden