Rockwell Automation Publication 2099-UM001D-EN-P - December 2012
151
Specifications and Dimensions
Appendix A
Circuit Breaker/Fuse Specifications
While circuit breakers offer some convenience, there are limitations for their use.
Circuit breakers do not handle high current inrush as well as fuses.
Make sure the selected components are properly coordinated and meet
acceptable codes including any requirements for branch circuit protection.
Evaluation of the short-circuit available current is critical and must be kept below
the short-circuit current rating of the circuit breaker.
Use class CC, T, RK1, or J fuses, with current rating as indicated in the table
below. The following fuse examples and short-circuit current ratings are
recommended for use with the 2099-BM
xx
-S drives when the Line Interface
Module (LIM) is not used.
Table 58 - 460V AC Input Drive Fuse and Motor Circuit Protector Specifications
Common DC Bus Fuse Specifications
Table 59 - Ferraz Shawmut Fuse Recommendations
IMPORTANT
LIM modules (catalog numbers 2094-BL
xx
S and 2094-XL75S-C
x
) provide
branch circuit protection to the Kinetix 7000 drive. Follow all applicable NEC
and local codes.
Drive Cat. No.
Bussmann
Fuse
Dual Element Time Delay
Fuse (min/max)
A rms
Non-Time Delay
Fuse (min/max)
A rms
Motor Circuit
Protector (max)
A rms
2099-BM06-S
LPJ-90SP
50/90
50/150
50
2099-BM07-S
LPJ-110SP
60/110
60/200
70
2099-BM08-S
LPJ-125SP
80/125
80/250
100
2099-BM09-S
LPJ-200SP
125/200
125/300
125
2099-BM10-S
LPJ-250SP
150/250
150/500
150
2099-BM11-S
LPJ-400SP
225/400
225/600
250
2099-BM12-S
LPJ-500SP
300/550
300/700
400
Drive Cat. No.
Drive Current
Rating (Adc)
Recommended
Fuse
Fuse Current
Rating
i²t (A²Sec)
Peak Let-Through Current
at 100kA rms
Pre-Arc
Max. Clearing @
600V AC
2099-BM06-S
42.9
HSJ80
80
1600
15000
7000 A
2099-BM07-S
55.7
HSJ90
90
2300
21000
7400 A
2099-BM08-S
69.7
HSJ100
100
2700
23000
7700 A
2099-BM09-S
105
HSJ175
175
8000
60000
12000 A
2099-BM10-S
137
HSJ200
200
14000
92000
13000 A
2099-BM11-S
204
HSJ400
400
63000
450000
21000 A
2099-BM12-S
281
HSJ400
400
63000
450000