Rockwell Automation Publication 193-UM014C-EN-P - August 2016
33
Configure the EtherNet/IP Communication Auxiliary Module
Chapter 2
EtherNet/IP communication auxiliary module back to their original position
and cycle power. The EtherNet/IP Communication Auxiliary Web Server will
be disabled unless it was permanently enabled.
Permanently Enabling the Web Server
In Administrative Mode, you can change any configuration parameter of the
EtherNet/IP communication auxiliary module, including permanently
enabling the embedded web server by following these steps:
1. Enter Administrative Mode by turning the rotary dials to 000 and cycle
power on the EtherNet/IP communication auxiliary module
2. Access the web page
3. Navigate to Administrative Settings->Network Configuration
4. You will be prompted for a user name and password. The default user
name is Administrator, and the default password is <blank>. Enter
“Administrator” as the user name, and leave the “password” field blank as
shown in the following picture.
5. Enable the Web Server Control and press “Apply Changes”.