Chapter 2
Configure the EtherNet/IP Communication Auxiliary Module
6. Click Next to register the device.
7. Click Finish to successfully register the module.
Web Server
Use the embedded web server of the EtherNet/IP communication auxiliary
module to configure the DeviceNet scanner and view diagnostic information
of the EtherNet/IP communication auxiliary module. As a security precaution
the embedded web server of the EtherNet/IP Communication Auxiliary is
disabled by default. To temporarily enable the web server, you must enter into
Administration Mode. To do this, set the rotary dials located on the front of
the EtherNet/IP communication auxiliary module to 000 and cycle power.
The device will then go online with the IP address used at the time of the
previous startup.
After you have made all configuration changes, exit Administration Mode and
return to Operation Mode by setting the rotary dials located on the front of the