2–3
How to Install Your Analog Module
Publication 17946.5.2 - May 1996
Methods of wiring the terminal base units are shown in the
illustration below.
Wiring when total current draw is less than 10A
Wiring when total current draw is greater than 10A
Daisychaining
Individual
Total current draw through any base unit must not be greater than 10A
Combination
24V dc
24V dc
24V dc
24V dc
24V dc or
120V ac
24V dc
ATTENTION: Do not daisy chain power or
ground from an analog terminal base unit to any ac
or dc discrete module terminal base unit.
!
Note:
Use this configuration if using any
noisy" dc discrete I/O modules in your system.
Analog module wiring separate from discrete wiring.
Analog Module
Note: All modules powered by the same power supply
must be analog modules for this configuration.
Note:
All modules must be analog modules for this configuration.
Analog Module
Discrete
Module
Discrete
Module
Discrete
Module
Discrete
Module
Analog Module
Analog Module
Analog Module
Analog Module
Analog Module
Analog Module