Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
31
Install a 1769 DeviceNet Communication Module
Chapter
2
Connect the Module to a
DeviceNet Network
Follow these steps to wire the DeviceNet connector.
1.
Connect the DeviceNet cable to the removable connector as shown.
2.
Insert the removable female connector into the mating male connector on
the DeviceNet scanner module.
3.
Screw the removable connector to the scanner case with the upper and
lower mounting screws with a torque of 0.6…0.7 N•m (5…6 lb•in).
Set the Node Address
Set the node address using one of these methods:
•
For the 1769-ADN, use the node address rotary switches as described in
Set the Node Address of a 1769-ADN Module
•
For the 1769-SDN, use RSNetWorx for DeviceNet software as described
in
Set the Node Address of a 1769-SDN Module
. The 1769-SDN module
has no hardware mechanism to set its address.
DeviceNet Connector
Connect Wire
(1)
(1) DeviceNet cable colors are shown on
the wiring label on the front of the
scanner.
To
Red
V+
White
CAN High
Bare
Shield
Blue
CAN Low
Black
V-
Grounding Screw
Use 2.08 mm
2
(14 AWG) wire
to connect to panel ground.
Comm Adapter
MS
IO
NS
DIAG
DeviceNet Connector
1769-ADN
1769-SDN
IMPORTANT
If the 1769-SDN module is the first or last device connected to the
DeviceNet network trunkline, be sure to add a termination
resistor (120
Ω
1%
≥
¼W resistor, Allen-Bradley catalog number
1485A-C2) across the blue (CAN Low) and white (CAN High)
wires.
Summary of Contents for 1769-SDN
Page 1: ...Installation Instructions DeviceNet Modules Catalog Numbers 1756 DNB 1769 ADN 1769 SDN...
Page 4: ...4 Rockwell Automation Publication DNET IN001B EN P January 2012 Summary of Changes Notes...
Page 8: ...8 Rockwell Automation Publication DNET IN001B EN P January 2012 Preface Notes...
Page 65: ......
Page 66: ......
Page 67: ......