background image

34

    1769-L32E, 1769-L35E CompactLogix Controller 

Publication

 1769-IN020-C-EN-P - July 2007

Module Status (MS) indicator

Condition

Status

Indicates

Recommended Action

Off

No power

The controller does not have 
power.

Check the controller power supply. 

Flashing green

Standby

The port does not have an IP 
address and is operating in 
BOOTP mode.

Verify that the BOOTP server is 
running.

Solid green

Ok

The port is operating 
correctly.

Normal operation. No action 
required.

Solid red

Held in reset

The controller is holding the 
port in reset or the controller 
is faulted.

Clear the controller fault. 

 

Replace the controller.

Self-test

The port is performing its 
power-up self-test.

Normal operation during 
power-up. No action required.

Major fault

An unrecoverable fault has 
occurred.

Cycle power to the controller.

 

Replace the controller.

Flashing red 

Updating 
firmware

The port firmware is being 
updated.

Normal operation during firmware 
update. No action required.

[email protected]

Summary of Contents for 1769-L32E CompactLogix 5332E

Page 1: ...1769 BA Battery 7 Install a 1784 CF64 or 1784 CF128 Industrial CompactFlash Card optional 9 Assemble the System 9 Mount the System 11 Make RS 232 Connections to the Controller 15 Make Ethernet Connec...

Page 2: ...769 IN020 C EN P July 2007 About This Publication Use this document as a guide to install the CompactLogix controller CompactFlash Card Status Indicator 33 Module Status MS indicator 34 Additional Res...

Page 3: ...utomation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information c...

Page 4: ...orable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst me sont sujettes inspection par les autori...

Page 5: ...pecific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must have suitable flame retardant...

Page 6: ...O bank requires its own power supply Only one controller can be used in a CompactLogix system A 1769 ECR right end cap or 1769 ECL left end cap is required to terminate the end of the communication b...

Page 7: ...Do not touch circuit components inside the equipment Use a static safe workstation if available Store the equipment in appropriate static safe packaging when not in use ATTENTION The 1769 BA battery...

Page 8: ...onnector port The connector is keyed to be installed with the correct polarity 3 Insert the battery into the battery port in the battery door 4 Slide the battery door back until it clicks into positio...

Page 9: ...e the CompactFlash card push the locking tab away from the CompactFlash card and pull the CompactFlash card from the socket Assemble the System The controller can be attached to an adjacent I O module...

Page 10: ...odules together 4 Move the module back along the tongue and groove slots until the bus connectors line up with each other 5 Use your fingers or a small screwdriver to push the module s bus lever back...

Page 11: ...es as shown This provides ventilation and electrical isolation ATTENTION When attaching the controller power supply and I O modules make sure the bus connectors are securely locked together to be sure...

Page 12: ...on cables can be used on either the right or left end A 1769 ECR right end cap or 1769 ECL left end cap terminates the end of the communication bus ATTENTION This product is grounded through the DIN r...

Page 13: ...e assembled modules as a template carefully mark the center of all module mounting holes on the panel 3 Return the assembled modules to the clean work surface including any previously mounted modules...

Page 14: ...latches will momentarily open and lock into place TIP If you are mounting more modules mount only the last one of this group and put the others aside This reduces remounting time when you are drillin...

Page 15: ...the other end of the cable an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding 2 R...

Page 16: ...efault Protocol DF1 full duplex Communication Rate 19 2 Kbps Parity None Station Address 0 Control Lines No Handshaking Error Detection BCC Embedded Responses Auto Detect Duplicate Packet Message Dete...

Page 17: ...at the default communication configuration is active TIP The default communication push button is recessed Before pressing the default communication push button be sure to note the present communicati...

Page 18: ...ble to the Ethernet port top port CH1 on the controller WARNING If you connect or disconnect the communications cable with power applied to this module or any device on the network an electrical arc c...

Page 19: ...ess The BOOTP utility is a standalone program that is located in one of the following directories RSLinx Tools directory in the Rockwell Software program folder on the Start menu the utility is automa...

Page 20: ...of the device you want to configure The New Entry dialog displays the device s Ethernet Address MAC 6 Enter the IP address TIP The hardware address is on the sticker located on the left side circuit...

Page 21: ...the configuration you assigned and does not issue a BootP request Use RSLinx software to set the IP address You can use RSLinx software version 2 41 or later to set the IP address 1 Make sure the con...

Page 22: ...CompactLogix Controller Publication 1769 IN020 C EN P July 2007 5 Right click the Ethernet port not the controller and select Module Configuration 6 Select the Port Configuration tab s a l e s r o c...

Page 23: ...tion type 8 Enter the IP address network subnet mask and gateway address if needed Use RSLogix 5000 software to set the IP address You can use RSLogix software to set the IP address 1 Make sure the co...

Page 24: ...e In the Controller Organizer select properties for the Ethernet port 4 Choose the Port Configuration tab 5 Specify the IP address 6 Click Apply 7 Click Ok This sets the IP address in the hardware Thi...

Page 25: ...e In order to update the firmware you must have the revision 1 EDS file 0001000E00410100 eds installed for the controller The EDS files are available on the RSLogix 5000 Enterprise Series software CD...

Page 26: ...nload it from the support website Go to http support rockwellautomation com Follow these steps to download firmware from the support website 1 In the left column frame click Technical Support 2 Click...

Page 27: ...g number of the controller and click Next 5 Expand the network until you see the controller 6 If the required network is not shown first configure a driver for the network in RSLinx software 7 Choose...

Page 28: ...catalog number of the controller and click Next 4 Expand the network until you see the controller If the required network is not shown first configure a driver for the network in RSLinx software 5 Cho...

Page 29: ...s 1 Use RSLogix 5000 software to store the controller user program and firmware of a currently configured controller to the CompactFlash card 2 Access the Nonvolatile Memory tab of the Controller Prop...

Page 30: ...position Prog Disable outputs Upload download projects Create modify and delete tasks programs or routines The controller does not execute scan tasks while the keyswitch is in the Prog position You c...

Page 31: ...een forced to an On or Off state but the forces have not been enabled BAT Off The battery supports memory Solid red Either the battery is not installed 95 discharged and should be replaced I O Off Eit...

Page 32: ...online with RSLogix 5000 software Solid red The controller detected a nonrecoverable fault so it cleared the project from memory Follow these steps to recover 1 Cycle power to the chassis 2 Download...

Page 33: ...n RS 232 activity CH1 Off No RS 232 activity Flashing green RS 232 activity ATTENTION Do not remove the CompactFlash card while the controller is reading from or writing to the card as indicated by a...

Page 34: ...The port is operating correctly Normal operation No action required Solid red Held in reset The controller is holding the port in reset or the controller is faulted Clear the controller fault Replace...

Page 35: ...l operation No action required Solid red Duplicate IP address The port has detected that the assigned IP address is already in use Verify that all IP addresses are unique Flashing Red green Self test...

Page 36: ...dissipation 2 61 W Power supply distance rating 4 The controller must be within four slot positions of the power supply North American temp code T4A Battery 1769 BA Weight approx 0 30 kg 0 66 lb Prog...

Page 37: ...Test Fc Operating Operating 5 g 10 500 Hz Shock IEC 60068 2 27 Test Ea Unpackaged Shock DIN rail mount Panel mount Operating 20 g Nonoperating 30 g Operating 30 g Nonoperating 40 g Emissions CISPR 11...

Page 38: ...n 89 336 EEC EMC Directive compliant with EN 50082 2 Industrial Immunity EN 61326 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2...

Page 39: ...ogix5000 Controllers General Instructions Reference Manual publication 1756 RM003 Programming the controller for sequential applications Logix5000 Controllers Process Control and Drives Instructions R...

Page 40: ...rs of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your module up and running New Produ...

Reviews: