Compact 1769-ASCII Module
33
Publication
1769-IN068B-EN-P - May 2005
Troubleshoot with Error Codes
Configuration Error Codes
Value (Hex)
Meaning
0
No error
200…3FF
Hardware error
400…5FF
Configuration error
800…DFF
Reserved for future use
E00…FFF
Bus master detected error
Value
(Hex)
Meaning
Description
Global Module Errors
0
No error
The 1769-ASCII module adds no
module-specific errors.
401
Max output array size exceeded
The maximum output array size is too
large.
In alternating mode, channel 0 and
channel 1 must have less than 496
transmit characters.
In simultaneous mode, channel 0 and
channel 1 must have less than 496
transmit characters collectively.
402
Max input array size exceeded
The maximum input array size is too
large.
In alternating mode, channel 0 and
channel 1 must have less than 496
receive characters.
In simultaneous mode, channel 0 and
channel 1 must have less than 496
receive characters collectively.