Rockwell Automation Publication 1756-UM013B-EN-P - October 2019
Chapter 5
Configure and Replace Safety Modules
Scenario 2 - Replacement Device SNN is Different from Original and Safety Signature Exists
1. Remove the old I/O device and install the new device.
2. Right-click your safety I/O device and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. On the Logix Designer application Dialog, click Yes.
6. On the next Logix Designer application Dialog, click Yes.