Allen-Bradley 1756-PA30XT Original Instructions Manual Download Page 8

8

Rockwell Automation Publication 1756-IN619E-EN-P - September 2019

ControlLogix Power Supply

Optional Power Cable Connection

The 1756-PA50, 1756-PA50K, 1756-PB50, 1756-PB50K, 1756-PA30XT, and 1756-PB30XT power supplies offer an optional cable retention 

mechanism.
Install the optional cable retention mechanism per the following procedure.

1. Align the power cable in the v-groove at the front of the power supply.
2. Feed a cable tie through the retainer on the v-groove.
3. To secure the power cable, tighten the cable tie.
4. Trim any excess cable tie length as appropriate.

Remove the Protective Label

Remove the protective label from the top of the power supply.

ATTENTION: 

Make sure the chassis is mounted and all panel fabrication is complete before you remove the protective label. This label protects the power supply 

from metal shavings falling inside the power supply and damaging it during operation.

Power Cable

V-groove

Cable Tie

Cable Tie

Summary of Contents for 1756-PA30XT

Page 1: ...he power supply that you can use This table lists the chassis that can be installed with each power supply Topic Page Summary of Changes 5 Tools Required 6 Install the Power Supply 6 Connect the Power...

Page 2: ...ti nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cablaggio...

Page 3: ...plicable for explanations of the degrees of protection provided by different types of enclosures Prevent Electrostatic Discharge ATTENTION Thisequipmentissensitivetoelectrostaticdischarge whichcancaus...

Page 4: ...ctions that mate to this equipment by using screws sliding latches threaded connectors or other means provided with this product Substitution of components may impair suitability for Class I Division...

Page 5: ...1325026X IECEx UL 14 0008X 1756 PC75 None 1756 PH75 1756 PH75K None 1756 PAXT None 1756 PBXT Ex nA IICT4 Gc DEMKO13ATEX1325026X IECEx UL 14 0008X 1756 PA30XT None 1756 PB30XT Ex nA IICT4 Gc DEMKO13ATE...

Page 6: ...flush with the front of the chassis 4 Tighten the top and bottom screws to fasten the power supply to the chassis 3 18 mm 0 125 in slotted screwdriver Crimper 6 35 mm 0 25 in slotted or 2 Phillips scr...

Page 7: ...ing ATTENTION Do not wire more than one conductor on any single terminal Use 15 A time delay type fuse in all ungrounded power connections IMPORTANT The voltage input connections of the power supplies...

Page 8: ...groove at the front of the power supply 2 Feed a cable tie through the retainer on the v groove 3 To secure the power cable tighten the cable tie 4 Trim any excess cable tie length as appropriate Rem...

Page 9: ...e power 3 Loosen the screws that secure the power supply to the chassis See step 4 on page 6 for the location of the screws on the power supply 4 Slide the power supply out so that the rear connector...

Page 10: ...ure type rating None open style Torque 0 565 N m 5 lb in Dimensions HxWxD approx 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in Wire size 2 5 mm2 14 AWG solid or stranded copper wire rated at 90 C 194 F...

Page 11: ...13 F Ta 158 F Temperature surrounding air max 70 C 158 F Enclosure type rating None open style Torque 0 565 N m 5 lb in Dimensions HxWxD approx 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in 14 0 x 7 8 x...

Page 12: ...ion needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ e...