66
Rockwell Automation Publication 1756-PM004D-EN-P - September 2012
Chapter 4
Data Access Control
Configure External Access
You configure external access from a menu when you create a new tag or data
type. You can also modify that value just like other tag attributes. These changes
can be made throughout the application. For example, they can be made in the
User-defined Data Type Editor, New Tag Dialog, and the Tag Properties Dialog.
External Access Options
You can choose one of three options—Read/Write, Read Only, None from the
External Access box on the following Logix Designer dialog boxes:
•
)
•
)
The default value in the External Access box is dependent on the usage, and type
of the tag. The following table describes the values.
External Access Settings
Description
Read/Write
External applications and devices have full access to the tag and can read and
change the tag’s value.
Read Only
External applications can read, but cannot change, the tag’s value.
None
External applications cannot read or change the tag’s value.
IMPORTANT
The Logix Designer application has full access to all tags, regardless of their
External Access settings. External access applies to all program, controller, and
Add-On Instruction scoped tags.
If the controller is in safety locked mode, only the safety tags will be disabled from
being accessed. The standard tags will have the same behavior as in the unlocked
mode.
If the tag is
Default value is
Alias
Same as its target. See Important note below.
Controller/program scoped and equipment phase input
parameters
Out-of-box is Read/Write.
Thereafter, when creating a new tag, the default external
access tag retains the value of the user’s previous
choice.
(1)
(1)
The External Access default value for tag creation is stored per Windows login account.
Equipment phase output parameters
Out-of-box is Read Only.
Thereafter, when creating a new tag, the default external
access tag retains the value of the user’s previous
choice.
Summary of Contents for 1756-L65 ControlLogix 5565
Page 4: ...2 Rockwell Automation Publication 1756 PM004D EN P September 2012 Summary of Changes Notes...
Page 8: ...6 Rockwell Automation Publication 1756 PM004D EN P September 2012 Preface Notes...
Page 66: ...64 Rockwell Automation Publication 1756 PM004D EN P September 2012 Chapter 3 Force I O Notes...
Page 88: ...86 Rockwell Automation Publication 1756 PM004D EN P September 2012 Index...
Page 89: ......