Online Additions - ControlNet Considerations
ControlNet considerations that must be made depend upon the ControlLogix
ControlNet modules you are using.
1756-CNB and 1756-CNBR Modules
When you add I/O to the ControlNet network via the 1756-CNB or
1756-CNBR modules while online, these considerations must be made:
•
Digital I/O modules can be added as rack-optimized connections if the
parent module is configured with rack-optimized connections.
•
Digital I/O modules can also be added as direct connections.
•
Analog I/O modules can be added only as direct connections.
•
Disable the Change of State (COS) feature on digital input modules
because it can cause inputs to be sent more quickly than the RPI.
•
If you plan to add large amounts of I/O to the ControlNet network,
dedicate one ControlNet network for I/O. For the dedicated
ControlNet network, verify that there is little or none of the following:
–
HMI traffic
–
MSG traffic
–
Programming workstations
IMPORTANT
These ControlLogix modules
cannot
be added while online:
•
Motion modules (1756-MO2AE, 1756-HYD02, 1756-MO2AS, 1756-MO3SE,
1756-MO8SE, 1756-MO8SEG, 1756-M16SE)
•
1756-RIO
•
1756-SYNCH
•
1756-56AMXN
TIP
While you can add a new digital I/O module to an existing rack-optimized
connection, you cannot add rack-optimized connections while online.
Summary of Contents for 1756-L63XT
Page 4: ...4 Rockwell Automation Publication 1756 UM001O EN P October 2014 Summary of Changes Notes...
Page 18: ...18 Rockwell Automation Publication 1756 UM001O EN P October 2014 Preface Notes...
Page 136: ...136 Rockwell Automation Publication 1756 UM001O EN P October 2014 Chapter 8 I O Modules...
Page 210: ...210 Rockwell Automation Publication 1756 UM001O EN P October 2014 Index Notes...
Page 211: ......