110
Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
Appendix C
PFD Calculations for a SIL 2 System
1756-IH16ISOE
ControlLogix sequence of events module
x
2,150,720
4.650E-07
—
1.40099E-07
1756-IR6I
ControlLogix RTD input module
x
4,268,525
2.343E-07
—
1.39616E-07
1756-IT6I
ControlLogix thermocouple input module
x
3,957,824
2.527E-07
—
1.39654E-07
1756-IT6I2
ControlLogix enhanced thermocouple input module
x
2,720,046
3.676E-07
—
1.39893E-07
1756-OA16I
ControlLogix AC isolated output module
x
32,891,456
3.040E-08
—
1.392E-07
1756-OA8D
ControlLogix AC diagnostic output module
x
11,311,040
8.841E-08
—
1.39318E-07
1756-OB16D
ControlLogix DC diagnostic output module
x
8,884,374
1.126E-07
—
1.39367-07
1756-OB16E
ControlLogix DC electronic-fused output module
x
14,997,714
6.668E-08
—
1.39274E-07
1756-OB16I
ControlLogix DC isolated output module
x
7,388,160
1.35352E-07
—
1.39413E-07
1756-OB32
ControlLogix DC output module
x
2,681,316
3.730E-07
—
1.39904E-07
1756-OB8EI
ControlLogix DC fused output module
x
14,019,200
7.133E-08
—
1.39283E-07
1756-OX8I
ControlLogix contact output module
x
60,59,635
1.650E-07
—
1.39474E-07
1756-OW16I
ControlLogix isolated relay output module
x
13,695,899
7.301E-08
—
1.39286E-07
1756-OF8
ControlLogix analog output module
x
10,629,795
9.408E-08
—
1.39329E-07
1756-OF6CI
ControlLogix isolated analog output module
x
8,354,667
1.197E-07
—
1.39381E-07
1756-OF6VI
ControlLogix isolated analog output module
x
21,604,960
4.629E-08
—
1.39232E-07
1756-OF8H
ControlLogix HART analog output module
x
5,118,187
1.954E-07
—
1.39536E-07
1794-ACN15/D
(4)
FLEX I/O ControlNet adapter
x
8,223,684
1.126E-07
—
1.39385E-07
1794-ACNR15/D
(4)
FLEX I/O ControlNet redundant adapter
x
8,223,684
1.126E-07
—
1.39385E-07
1794-ACNR15XT/D
(4)
FLEX I/O-XT ControlNet redundant adapter
x
8,223,684
1.126E-07
—
1.39385E-07
1794-AENT/B
FLEX I/O EtherNet/IP adapter
x
1,779,827
5.6185E-07
—
1.40305E-07
1794-AENTR
(4)
FLEX I/O EtherNet/IP redundant adapter
x
1,268,070
7.886E-07
—
1.40799E-07
1794-AENTRXT
(4)
FLEX I/O-XT EtherNet/IP redundant adapter
x
1,268,070
7.886E-07
—
1.40799E-07
1794-IB16
FLEX I/O 16 sink input module
x
179,506,158
5.57084E-09
—
1.39151E-07
1794-1B16XT
(4)
FLEX I/O-XT 16 sink input module
x
16,300,000
6.13497E-08
—
1.39263E-07
1794-IJ2
FLEX I/O 2-channel counter module
x
55,344,640
1.80686E-08
—
1.39176E-07
1794-IJ2XT
(4)
FLEX I/O-XT 2-channel counter module
x
11714128
8.5367E-08
—
1.39311E-07
1794-IP4/B
FLEX I/O 4-channel counter module
x
220,227,200
4.53984E-08
—
1.39231E-07
1794-IB10XOB6
FLEX I/O 10 input/6 output module
x
100,000,000
0.00000001
—
1.39159E-07
1794-IB10XOB6XT
(4)
FLEX I/O-XT 10 input/6 output module
x
22,202,487
4.0504E-08
—
1.39231E-07
1794-OB8EP
FLEX I/O 8 protected output module
x
100,000,000
0.00000001
—
1.39159E-07
1794-OB8EPXT
FLEX I/O-XT 8 protected output module
x
2,389,669
4.18468E-07
—
1.4000E-07
1794-OB16
FLEX I/O 16 output module
x
54,322,632
1.84085E-08
—
1.39176E-07
1794-OB16P
FLEX I/O 16 protected output module
x
100,000,000
0.00000001
—
1.39159E-07
1794-OB16PXT
FLEX I/O-XT 16 protected output module
x
1,139,840
8.77316E-07
—
1.40995E-07
1794-OW8
FLEX I/O 8 relay output module
x
29,088,895
3.43774E-08
—
1.39208E-07
1794-OW8XT
FLEX I/O-XT 8 relay output module
x
1,312,973
7.6163E-07
—
1.40739E-07
1794-IE8/B
FLEX I/O 8 analog input module
x
18,914,770
5.28687E-08
—
1.39246E-07
Table 10 - PFD Calculations - 1-year for ControlLogix Component
Cat. No.
(1)
(2)
Description
61508
(2010)
Mean Time Between
Failure (MTBF)
(9)
λ
(10)
Calculated PFD
1oo1
Architecture
1oo2
Architecture
Summary of Contents for 1756-L6 Series
Page 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Page 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Page 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Page 133: ...Allen Bradley Motors ...