Publication 1764-UM001A-US-P
3-4
Installing and Wiring Your Module
Figure 3.4 JW3 Pin Assignments and Settings
Use the worksheet in appendix B to document the selected jumper setting of
jumper JW3. Documenting your selection provides others with information
necessary to integrate the module with their SLC 500 fixed or modular controllers.
Setting Jumper JW4
Use jumper JW4 to select one of the following configurations for the module ports:
•
PRT1 Port – Program port with
default
communication settings
PRT2 Port – ASCII interface port
DH485 Port – Run time DH485 operation only
•
PRT1 Port – ASCII interface port
PRT2 Port – ASCII interface port
DH485 Port – Program port with DH485 protocol
•
PRT1 Port – Program port with programmed communication settings
PRT2 Port – ASCII interface port
DH485 Port – Run time DH485 operation only
•
PRT1 Port – Program port with programmed communication settings
PRT2 Port – DF1 protocol
DH485 Port – Disabled
2
4
6
1 3
5
SLC 500
BASIC MODULE
CA
T
S
ER
SERIAL
NO.
FRN
JW1
1
2
3
4
5
6
7
8
9
U
L
PRT1
1
2
3
4
5
6
7
8
9
PRT2
SA
JW2
DH485
1747-M1 EEPROM (1746-BAS only)
1747-M2 EEPROM (1746-BAS only)
1747-M3 UVPROM (1746-BAS only)
1771-DBMEM1 EEPROM (1746-BAS-T only)
1771-DBMEM2 EEPROM (1746-BAS-T only)
(shipped configuration)
1747-M4 UVPROM (1746-BAS only)
Pin Assignments
ATTENTION
All other jumper settings for JW3 are illegal and may cause
damage to the module.
Summary of Contents for 1746-BAS
Page 4: ...Publication 1746 UM004A US P Summary of Changes ii...
Page 8: ...Publication 1746 UM004A US P Table of Contents iv...
Page 26: ...Publication 1746 UM004A US P 1 14 Module and Development Software Overview...
Page 34: ...Publication 1764 UM001A US P 2 8 Component Selection...
Page 70: ...Publication 176 UM04A US P A 4 Specifications...
Page 83: ...Spare Allen Bradley Parts...