
32
Rockwell Automation Publication 1734-UM007E-EN-P - October 2015
Chapter 4
Set and Operate Your Module
If either of these bits remain high, call technical support for further assistance.
You can monitor power, SSI data and clock wire faults, or major module faults by
monitoring a single bit in Status Byte 1; the IDF bit (bit 3 of Status Byte 1). We
recommend that you place the IDF bit in your ladder logic as an indicator of SSI
sensor data integrity. If the IDF bit is set to 1 for any of the reasons discussed
above, you can quickly switch your system to a safe state for troubleshooting.
Example of Using the 1734-
SSI Module with a 24-bit SSI
Sensor
See the diagram that illustrates the SSI clock (CLK) signal that is sent to the SSI
sensor by the 1734-SSI module and the SSI data (DATA) coming back to the
module from the sensor.
The CLK and DATA signals are representative of what you could actually see on
an oscilloscope when the module is attached to a SSI sensor in a live system. The
SSI module must be configured for a SSI Word length of 24, as well as the proper
Data Rate and SSI Word Delay time stated in the SSI sensor specifications.
SSI Word Delay time is approximately equal to a value called monoflop time, as
stated by some SSI sensor manufacturers. When configuring the 1734-SSI
module, enter the monoflop time value for SSI Word Delay time.
Point A of the CLK signal is a falling clock edge. When the SSI sensor sees the
first falling clock edge after a delay period, it knows to latch its current position
into a parallel-to-serial converter located in the sensor.
At point B of the CLK signal is the rising clock edge. The sensor begins to send
its serial data to the 1734-SSI module. The module actually starts reading the
sensor position data on the next rising clock edge, denoted by MSB in the figure
above. MSB is the most significant bit of the data word.
0
0
1
1
1
0
0
0
0
1
0
0
1
0
0
1
0
1
1
1
0
1
0
1
1
C
2
9
E
A
CLK
DATA
A B
MSB
LSB
SSI WORD DELAY
TIME
t
p