Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
148
Troubleshoot with the Indicators
1734-IE2V Analog Voltage Input Module
1734-OE2V Analog Voltage Output Module
41974
Module Status
Network Status
Status of Input 0
Status of Input 1
Analog
Voltage
Input
Module
Status
Network
Status
1734
IE2V
NODE:
0
1
Indication
Probable Cause
Recommended Action
Channel Status
Off
Module is in CAL mode.
None.
Solid green
Normal operation present with channel scanning inputs.
None.
Flashing green
Channel being calibrated.
None.
Solid red
No power or major channel fault present.
Apply field power, or replace module, as needed.
Flashing red
Channel is at end of range (-0.25, -10.25, or +10.25V).
Operate within normal range.
41974
Module Status
Network Status
Status of Output 0
Status of Output 1
Analog
Voltage
Output
Module
Status
Network
Status
1734
OE2V
NODE:
0
1
Indication
Probable Cause
Recommended Action
Channel Status
Off
Module is in CAL mode.
None.
Solid green
Normal operation present with channel actively controlling outputs.
None.
Flashing green
Channel being calibrated.
None.
Flashing red
A Low or High Clamp alarm is present.
Operate within normal range.
Solid red
No field power is present.
Apply field power.
Summary of Contents for 1734-OB2
Page 4: ...Publication 1734 UM001E EN P July 2013 iv Summary of Changes Notes...
Page 16: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 xxiv Notes...
Page 22: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 6 About the Modules Notes...
Page 116: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 118 POINT I O Module Data Notes...
Page 168: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 176 Default Data Maps Notes...
Page 172: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 180 Mounting Dimensions Notes...