Troubleshoot with the Indicators
147
Troubleshoot Analog
Modules
Each analog module has I/O indicators to show the status of the inputs/outputs.
Refer to the individual module for I/O status information.
1734-IE2C Analog Current Input Module
1734-OE2C Analog Current Output Module
41974
Module Status
Network Status
Status of Input 0
Status of Input 1
4-20mA
Analog
Input
Module
Status
Network
Status
1734
IE2C
NODE:
0
1
Indication
Probable Cause
Recommended Action
Channel Status
Off
Module is in CAL mode.
None.
Solid green
Normal operation present with channel scanning inputs.
None.
Flashing green
Channel being calibrated.
None.
Solid red
No power or major channel fault present.
Apply field power, or replace module, as needed.
Flashing red
Channel is at end of range (0 mA or 21 mA).
Operate within normal range.
41974
Module Status
4-20mA
Analog
Output
Module
Status
Network
Status
1734
OE2C
NODE:
0
1
Network Status
Status of Output 0
Status of Output 1
Indication
Probable Cause
Recommended Action
Channel Status
Off
Module is in CAL mode.
None.
Solid green
Channel actively controlling outputs
None.
Flashing green
Channel calibrating.
None.
Solid red
Unrecoverable fault may require device replacement.
Replace device.
Flashing red
No power, or open wire present.
Apply power or verify wiring to load, and correct, as needed.
Summary of Contents for 1734-OB2
Page 4: ...Publication 1734 UM001E EN P July 2013 iv Summary of Changes Notes...
Page 16: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 xxiv Notes...
Page 22: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 6 About the Modules Notes...
Page 116: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 118 POINT I O Module Data Notes...
Page 168: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 176 Default Data Maps Notes...
Page 172: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 180 Mounting Dimensions Notes...