Status Indicators
Chapter
9
Module Status
Network Status
Configuration Lock
Indicator
Status
Description
Recommended Action
MS
Off
No power is applied to the module.
Apply power to this connector.
Solid green
The module is operating normally.
None.
Solid red
The module detected an unrecoverable fault.
Cycle power to the module. If problem persists, replace the
module.
Flashing
green
Device is in the Idle or Standby state.
Configure the module and establish connection.
Flashing red
The module has detected a recoverable fault.
Cycle power to the module or reset the module.
User-initiated firmware update is in progress.
Wait for firmware update to complete.
Flashing red
and green
Module is unconfigured.
Reconfigure the module. For additional information,
inspect Network Status indicator.
The module is performing its power-cycle diagnostic tests.
Wait for the module to complete its power-cycle
diagnostics.
Indicator
Status
Description
Recommended Action
NS
Off
The module is not online with the network or there is no
power.
Verify your network is working properly.
Flashing
green
Module online with no connections in established state.
Verify your network and module configuration.
The module identified the communication rate of the
network but no connections are established.
Solid green
Module online with connections in established state. The
module is operating normally.
None.
Flashing red
One or more I/O connections is in timed-out state.
Verify your network and module configuration.
A user-initiated firmware update is in progress.
Wait for firmware update to complete.
Solid red
Critical link failure. The module detected an error that
prevents it from communicating on the network, such as a
duplicate node address.
Cycle power to the module. Check node addressing.
Indicator
Status
Description
Recommended Action
LK
(1)
Off
No configuration or configured by a GuardLogix originator.
Validate configuration by a network configuration tool,
such as RSNetWorx software.
Invalid configuration data.
Solid yellow
Locked.
None.
Valid configuration, locked by a network configuration tool,
such as RSNetWorx software.
Flashing
yellow
Not locked.
None.
Valid configuration by a network configuration tool, such
as RSNetWorx software.
(1) Not applicable when used with GuardLogix controllers.