Rockwell Automation Publication 1606-RM105A-EN-P - July 2020
13
Functional Diagram
Terminals and Wiring
The terminals are IP20 fingersafe constructed and suitable for field and
factory wiring.
When wiring terminals, be aware of these considerations:
•
Use appropriate copper cables that are designed for minimum
operating temperatures of:
- 60 °C (140 °F) for ambient up to 45 °C (113 °F)
- 75 °C (167 °F) for ambient up to 60 °C (140 °F)
- 90 °C (194 °F) for ambient up to 70 °C (158 °F)
•
Follow national installation codes and installation regulations.
•
Ensure that all strands of a stranded wire enter the terminal
connection.
•
Securely tighten or close unused terminal compartments.
•
Use ferrules if needed. Ferrules are allowed.
Figure 10 - Functional Diagram
Buffer Capacitor
Charger &
Inrush Limiter
Buffer
Capacitor
Buffer Capacitor
Discharger
Status
LED
7 Active
6 (+)
Ready Monitor
+
-
Active Monitor
+
-
8 Ready
9 Inhibit
Opto-coupler
Buffer
Capacitor
Shut-Down
Input / Output
Voltage Monitor
Back-up
Level
Selector
Reverse-
Polarity
Protection
-
-
+
Safety and
Over-
Voltage
Protection
Chassis
Ground
Supply
Voltage
Opto-coupler
Opto-coupler
Attribute
Values for Supply Voltage
Values for Signals
Type Screw
terminals Pluggable screw terminals
Solid wire
16 mm
2
max (0.0248 in
2
max)
2.5 mm
2
max (0.0039 in
2
max)
Stranded wire
10 mm
2
max (0,0155 in
2
max)
2.5 mm
2
max (0.0039 in
2
max)
American Wire Gauge
22…8 AWG max
22…14 AWG
Wire diameter max
5.2 mm (including ferrules)
(0.20 in.) (including ferrules)
2.25 mm (including ferrules)
(0.09 in.) (including ferrules)
Wire stripping length
12 mm typ (0.5 in. typ)
6 mm (0.25 in.)
Tightening torque
2.3 N•m (20.5 lb•in)
0.4 N•m (3.5 lb•in)
Screwdriver
3.5 mm (0.14 in.) or 5 mm (0.20 in.) slotted
or cross-head No 2
3 mm (0.12 in.) slotted