Publication 0160-5.18 - June 2003
Using 160-DN2 with DeviceNet Scanner
6-21
Using I/O Messaging (Continued)
SLC Example
Figure 6.16
Example SLC Ladder Logic Program
0000
Copy File
Source
#M1:1:0
Dest
#N9:0
Length
128
CO P
0001
N9:0
1
Bulletin 160
RUNNING
Status Bit
O:3.0
0
1746-O*8
Operator Display
Drive Running
Status Bit
0002
7
1
0003
Move
Source
N9:1
0<
Dest
N21:1
0<
MOV
0004
I:2.0
0
1746-I*16
Operator Input
Drive Start
Command Bit
N10:0
1
Bulletin 160
START
Command Bit
0005
I:2.0
1
0
0006
2
2
O:3.0
Operator Display
Drive Faulted
Status Bit
1746-O*8
N9:0
Bulletin 160
FAULTED
Status Bit
Operator Display
Drive Feedback
Status Word
Operator Input
Drive Stop
Command Bit
I:2.0
Operator Input
Drive Jog
Command Bit
1746-I*16
N10:0
Bulletin 160
STOP
Command Bit
N10:0
Bulletin 160
JOG
Command Bit
1746-I*16
The scanner gathers drive status data via the DeviceNet
network. The M-File is copied into the N9 data file in the SLC
to move the drive status information to a convenient location.
These rungs move the drive status from
the N9 data file to an operator display.
These rungs move the inputs of the
operator from the operator station to the
N9 data file. They will then be sent to the
scanner and out to the drive via the
DeviceNet network.
Summary of Contents for 160-DN2
Page 1: ...User Manual DeviceNet Communication Module Catalog Number 160 DN2 Firmware 3 xxx...
Page 8: ...iv Table of Contents Publication 0160 5 18 June 2003...
Page 80: ...Publication 0160 5 18 June 2003 7 6 Troubleshooting Notes...
Page 82: ...Publication 0160 5 18 June 2003 A 2 Specifications Notes...
Page 115: ......