Allen-Bradley 1492-CM1771-LD004 Manual Download Page 1

Field Wire Conversion Module for A-B 1771-ID16 to 1756-IA16I or 1756-IH16I
or 1771-IQ16 to 1756-IB16I

 Refer to conversion module Specifications Section: Maximum Operating Voltage

 This is cable length in meters. Available lengths are limited to 005 (0.5m) and 010 (1.0m). 

 

Conversion Module

 

Compatible 1771 

Input Module

 

Compatible 1756 

Input Module

 

Required 1492 Cable

 

1492-CM1771-LD004
1492-CM1771-LD004
1492-CM1771-LD004

1771-ID16
1771-ID16

1771-IQ16

1756-IA16I

1756-IH16I

1756-IB16I

1492-CONCAB

Y

1492-CONCAB

Y

1492-CONCAB

Y

PN-40377

DIR 10000045373 

(Version 00)

Printed in U.S.A.

(Cat 1492-CM1771-LD004)

Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. 
In the left margin click on Publications Library and Literature Library.  In the Search Area (right margin), Search by Catalog 
Number and in the Search box type in the catalog number of the conversion system component.

I. Module Description

    The 1492-CM1771-LD004 conversion module provides field wire signal conversion from an A-B 1771-ID16, 74 to 

138Vac or 105 to 138Vdc, 16 point individually isolated input module to a 1756-IA16I, 79 to 132Vac

, 16 point 

individually isolated input module or a 1756-IH16I, 90 to 146Vdc, 16 point individually isolated input module. The 
1492-CM1771-LD004 conversion module also provides field wire signal conversion from an A-B 1771-IQ16, 10 to 
32Vdc, 16 point individually isolated input module to a 1756-IB16I, 10 to 30Vdc

, 16 point individually isolated 

input  module. The  conversion  module  provides  the  mating  connector  to  the  1771-ID16  or  1771-IQ16  module 
swing-arm/terminal block with the attached field wires. It routes those signals via its 37-pin connector and a 

   1492-CONCAB

Y pre-wired cable to compatible terminals on the 1756-IA16I, 1756-IH16I or 1756-IB16I (refer to 

Wiring Diagrams on page 2, 3 and 4 for details).

II. Module Installation

The  1492-CM1771-LD004  conversion  module  must  be  installed  in  a  1492  conversion  base-plate  and  cover-plate 
assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the 
conversion assembly. For a list of compatible assemblies refer to Appendix A.

III. Conversion Module Compatibility Matrix

Conversion Compatibility and
Product I.D. Label

37-Pin Connector for cable 1492-CONCAB

Y

1492-CM1771-LD004 Conversion Module

De-energize and lockout any and all power to all I/O field devices connected to the A-B 1771 I/O chassis, 
and the power to the 1771 I/O chassis itself. Ensure all power is de-energized and locked out to any 
device in the control cabinet where the conversion is to be performed.  Ensure work is performed by 
qualified personnel.

WARNING