60
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Chapter 1
Install the XM-124 Standard Dynamic Measurement Module
• The ADR scanner cannot download the configuration data to an XM
module if the module has a saved configuration in its nonvolatile
memory. This happens because the saved configuration is restored and
the module enters Run mode when the power is cycled. (Configuration
parameters cannot be downloaded while an XM module is in Run
mode.) XM modules must be in Program mode for the ADR
configuration to be downloaded and this occurs only when there is no
saved configuration.
• An XM module enters Run mode automatically after the ADR scanner
restores the module’s configuration only if the module is in Run mode at
the time the configuration is saved to the scanner. If the module is in
Program mode when the configuration is saved, then the module
remains in Program mode after the ADR scanner downloads the
configuration.
• The ADR scanner saves and restores only the configuration parameters
contained in the EDS file of the module. Some XM parameters are not
included in the EDS file because they are not supported by either the
EDS specification or the tools that read the EDS files, for example
RSNetWorx for DeviceNet software. These configuration parameters
are not restored with ADR.
These configuration parameters are not included in the EDS file and
cannot be saved or restored with ADR:
– Channel Name
– Tachometer Name
– Alarm Name
– Relay Name
– All Triggered Trend related parameters
– All SU/CD Trend-related parameters
– Custom Assembly structure
TIP
To delete a saved configuration from nonvolatile memory, use the Delete
service in RSNetWorx™ for DeviceNet software or perform these steps in the
XM Serial.
1. From the File menu, choose Save As.
2. Enter a file name for the configuration.
3. Click OK.
4. Click the Module tab.
5. Click Reset to reset the module to factory defaults.
6. From the File menu, choose Open.
7. Select the configuration file and choose OK.
Make sure to disable auto save. From the Device menu, clear the Auto Save
Configuration check mark.
Summary of Contents for 1440-SDM02-01RA