Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
Figure 26 - Two IEPE Accelerometers and a Non-contact Sensor Wiring
Connect a Velocity Sensor and Two Non-contact Sensors
shows the wiring of a velocity sensor and two non-contact sensors to
the terminal base unit. The velocity sensor is wired to channel 1. The first non-
contact sensor is wired to channel 2, and the other non-contact sensor is wired
to the tachometer input signal.
IMPORTANT
Transducer DC bias is monitored on all signals.
Shield
Pin A - Si gn al
Pin B - Common
Cabl e s hiel d not
conn ecte d at thi s end
0
16
22
6
21
Channel 1 Input Signal
Signal Common
5
37
SIG
-24
COM
17
1
Signal Common
Channel 2 Input Signal
-24V DC
Pin A - Si gn al
Pin B - Common
Cabl e s hiel d not
conn ecte d at thi s end
Shield
36
20
4
Tach Input Signal
Signal Common
31
Shield
Shield
Fl oati ng
I solat ed Senso r Dr iv er
18
TYPICAL WIRING FOR TWO IFPF ACCELEROMETERS AND
NON-CONTACT SENSOR TO XM-124 STANDARD DYNAMIC MEASUREMENT MODULE
ATTENTION:
You may ground the cable shield at either end of the
cable. Do not ground the shield at both ends. Recommended practice
is to ground the cable shield at the terminal base and not at the
transducer. Any convenient chassis terminal may be used.
See
Terminal Block Assignments on page 28
IMPORTANT
Transducer DC bias is monitored on all signals.