138
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Appendix B
CIP Objects
Services
Band Measurement
Object (Class ID 31E
H
)
The Band Measurement Object models the measurement of the amplitude of a
signal within a narrow frequency range.
Class Attributes
The Band Measurement Object provides no class attributes.
Instances
There are 10 instances of this object. Instances 1…8 are the Band
measurements that are derived from the spectrum data. Instances 9 and 10 are
the Band Pass measurements that are performed in Band Pass Filter
measurement mode.
Table 63 - Alarm Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns one attribute.
10
h
Instance
Set_Attribute_Single
Sets one attribute.
(1)
(1) Attributes can only be set while the device is in Program mode. See the description of the Device Mode Object for more
information.
Table 64 - Band Measurement Object Instances
Instance
Description
1
Channel 1 Band Measurement #1
2
Channel 2 Band Measurement #1
3
Channel 1 Band Measurement #2
4
Channel 2 Band Measurement #2
5
Channel 1 Band Measurement #3
6
Channel 2 Band Measurement #3
7
Channel 1 Band Measurement #4
8
Channel 2 Band Measurement #4
9
Channel 1 Band Pass Measurement
10
Channel 2 Band Pass Measurement