136
Rockwell Automation Publication 1440-UM001D-EN-P - September 2016
Appendix B
CIP Objects
Services
Alarm Object (Class ID 31DH)
The Alarm Object mode is a two-stage (alert and danger levels) alarm.
Class Attributes
Instances
There are 16 instances of this object.
Instance Attributes
Table 60 - Acknowledge Handler Object Services
Service Code
Class/Instance Usage
Name
0E
h
Instance
Get_Attribute_Single
10
h
Instance
Set_Attribute_Single
Table 61 - Alarm Object Class Attributes
Attribute
ID
Access
Rule
Name Data
Type
Description
Semantics
1
Get
Revision
USINT
Version of the
implemented object.
2 (indicates that Threshold
Multiplier is a REAL instead of
USINT)
Table 62 - Alarm Object Instance Attributes
Attribute
ID
Access Rule
Name
Data Type
Description
Semantics
3
Get
Alarm Status
3 BITS
The status of the alarm.
0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
4
Get/Set
Alarm Enable
BOOL
Indicates whether this alarm object
is enabled.
0 = Disabled
1 = Enabled
5
Get
Type
USINT
Type of Alarm
0 = Magnitude
1 = Vector
6
Get
Threshold Units
USINT
Indicates whether the thresholds
and deadband value are specified in
units of measure. Not applicable to
vector alarms.
Set to 1
1 = Measurement units
7
Get/Set
AlarmCondition
USINT
Indicates on which side of the
threshold values the alarm and
danger conditions exist. Not
applicable to vector alarms.
0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range
Summary of Contents for 1440-SDM02-01RA