60
Rockwell Automation Publication 1420-UM001E-EN-P - March 2016
Appendix A
PowerMonitor 500 Unit Data Tables
Table 31 - Configuration - Digital Relay Outputs: Read and Write
Modbus
Address
Length
(words)
Description / Units
Data Format
Notes
304865
1
Digital output channel 1: enabling
UINT
0=Remote
1=Alarm
2= Pulse
304866
1
Digital output channel 1: output
working mode
UINT
0=NO
1=NC (only if selected ‘Alarm’ type)
304867
1
Digital output channel 1: linked
alarm
UINT
0=AL1
1=AL2
2=AL3
3=AL4 (only if selected ‘Alarm’ type)
304868
1
Channel 1: linked counter-variable
UINT
0=Total kWh+
1=Total kVARh+
2=Total kWh-
3=Total kVARh-
4=Partial kWh+
5= Partial kVARh+
6= Partial kWh-
7= Partial kVARh-
304869
2
Digital output channel 1: pulse
REAL
Pulse weight (kWh/pulse or kVARh/pulse)
Value min = 0.001
Value max = 9999.9
304871
1
Digital output channel 2: enabling
UINT
0=Remote
1=Alarm
2= Pulse
304872
1
Digital output channel 2: output
working mode
UINT
0=NO
1=NC (only if selected ‘Alarm’ type)
304873
1
Digital output channel 2: linked
alarm
UINT
0=AL1
1=AL2
2=AL3
3=AL4 (only if selected ‘Alarm’ type)
304874
1
Channel 2: linked counter-variable
UINT
0=Total kWh+
1=Total kVARh+
2=Total kWh-
3=Total kVARh-
4=Partial kWh+
5= Partial kVARh+
6= Partial kWh-
7= Partial kVARh-
304875
2
Digital output channel 2: pulse
REAL
Pulse weight (kWh/pulse or kVARh/pulse)
Value min = 0.001
Value max = 9999.0
Summary of Contents for 1420-V1
Page 4: ...4 Rockwell Automation Publication 1420 UM001E EN P March 2016 Summary of Changes Notes...
Page 6: ...6 Rockwell Automation Publication 1420 UM001E EN P March 2016 Table of Contents Index 85...
Page 46: ...46 Rockwell Automation Publication 1420 UM001E EN P March 2016 Chapter 4 Communication Notes...
Page 88: ...88 Rockwell Automation Publication 1420 UM001E EN P March 2016 Index Notes...
Page 89: ......