Detailed CGCM-DLR Unit Tag Descriptions
Appendix
E
Redundancy Outputs from CGCM-DLR Unit
•
CGCM_Flt
- This tag indicates, if the CGCM-DLR unit is still capable,
that the CGCM-DLR unit has a detected an internal failure.
•
CGCMInControl
- This tag indicates that the CGCM-DLR unit has
hardware and software excitation enabled.
•
Spare1
- When operating in Redundant mode, this tag indicates the
CGCM-DLR unit has assumed the role of primary and is providing
excitation to the generator.