214
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Appendix D
Specifications
Over-excitation Voltage Protection
Over-current Protection
Undervoltage Protection
Overvoltage Protection
Loss of Sensing Protection
Attribute
Range
Increment
Pickup
1…200V DC
1V DC
Time delay
0.1…30 s
0.1 s
Attribute
Range
Increment
Accuracy
Pickup
10…320% of rated
generator current
1%
±2% rated current
Time delay
Characteristic inverse
per ANSI C50.13
configurable
0.1 s
Attribute
Range
Increment
Accuracy
Pickup
60…100% of rated
generator voltage
1%
±2% rated voltage
Time delay
0.1…300 s
±0.1 s
Attribute
Range
Increment
Accuracy
Pickup
100…140% of rated
generator voltage
1%
±2% rated voltage
Time delay
0.1…300 s
±0.1 s
Attribute
Value
Pickup
See text description in Operation section of the manual for this item
Time delay
0.1 s for normal operation, 1 s during soft start