Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
115
CGCM-DLR Unit Configuration
Chapter
4
•
Validate and graph button – Updates the graph that is shown on the
Current tab to display the selected over-current characteristic curve. The
specific curve that is selected by the over-current time dial setting is
displayed in black.
Related Parameters
•
GenRated_I
•
GenRated_V
Frequency Page
The Frequency page is used to configure the parameters that are related to the
over-frequency and under-frequency protection functions.
•
Over-frequency setpoint - Establishes the generator over-frequency
setpoint. The tag
OvrFreqSetpt
in the configuration table stores this
parameter, expressed in Hz.
•
Over-frequency Delay - Establishes the amount of time in seconds that the
frequency must be above the over-frequency setpoint before the
CGCM-DLR unit annunciates the fault. This parameter is stored in tag
OvrFreqTimeDly
in the configuration table.
•
Under-frequency setpoint - Establishes the generator under-frequency
setpoint. The tag
UndrFreqSetpt
in the configuration table stores this
parameter, expressed in Hz.