18
The desired combustion power is selected by pressing the P4 and P6 keys. Press the P3 key to save the new parameter set
value. To cancel all modifications and return to the old values, press the P1 key.
10.3.1.2 Combustion Recipe
Combustion Recipe Menu. If only one recipe is set at the factory, this menu is not available.
10.3.1.3 Auger Calibration
This menu is used for changing the auger feeding rate. The system has 10 calibration steps (from -5 to +5, the factory
default is 0). The calibration effect is valid in the Run Mode and in the Modulation. For each step, the value is increased or
decreased by 5%.
Example: Calibration value = -2; (-2 * 5% = - 10%) This means that the calibrated velocity values of the auger will be
reduced by 10% compared to the factory values.
Factory set values
C03=600
C04=900
C05=1200
C06=1600
C07=2000
C11=600
Calibrated values
C03=540
C04=810
C05=1080
C06=1440
C07=1800
C11=540
10.3.1.4. Combustion Fan Calibration
This menu is used for changing the number of revolutions of the combustion fan. The system has 10 calibration steps
(from -5 to +5, the factory default is 0). The calibration effect is valid in the Run Mode and in the Modulation. For each step, the
value is increased or decreased by 5%.
Example: Calibration value = + 3; (+ 3 * 5% = + 15%). This means that the calibrated combustion fan speed values will be
increased by 15% compared to the factory values.
Factory set values
U03=1000
U04=1200
U05=1400
U06=1600
U07=1800
U11=900
Calibrated values
U03=1150
U04=1380
U05=1610
U06=1840
U07=2070
U11=1030
Note: The calibration of the auger and flue gas motor should not be carried out without prior consultation with the
authorized maintenance staff or representative of the manufacturer.
Heating Management Menu
This is a menu for setting the parameters that determine the heating performance of the boiler . It contains several
submenus. By pressing the P3 key you enter the menu and you can see the following submenus:
10.3.2.1. Boiler Thermostat
This menu allows you to adjust the so-called set water temperature in the boiler. The temperature range of the water in the
boiler can be adjusted from 30 ° C to 80 ° C. By adjusting the set value of the water temperature in the boiler, the user sets the
operating condition of the boiler, i.e. the boiler will operate at the set power until it reaches the set water temperature in the
boiler. When the set value of the water temperature in the boiler is reached, the boiler goes into the state of modulation i.e. it
continues to operate at minimum power.
We do not recommend setting the water temperature below 57ºC due to possible condensation of the boiler, nor over 75ºC.
10.3.2.2. Buffer Thermostat
This menu allows the buffer temperature to be modified. This menu is only active if the buffer is installed.
10.3.2.3. Room thermostat
In this menu, the ambient probe temperature is modified. This menu is only visible if the ambient probe option or room
thermostat has been activated.
10.3.2.4. Summer – Winter
In this menu, the functionality of the boiler is changed depending on the season. The display shows one of two symbols:
.
10.3.2.5 Heating Power
Currently set power: Power 1