Filling up and bleeding the heating circuit 

2.6.2

 

Attach the long provided filing hose between the filling valves, to fill up the heating 
circuit. 
 

 

Open the valves 

Heating circuit supply

 and 

Heating circuit return

 

 

Open the filling valves. 
 

 

Fill up the system until the manometer shows 1,6 Bar. 
 

 

Close the filling valves. 
 

 

Bleed the heating system via the draining valves and at the heating systems draining 
places e.g. radiator valves. 
 

 

If the pressure is low after bleeding the system, open the filling valves and fill up to 
1,6 Bar again. 
 

 

The first time the heating system is filled up, this procedure might have to be 
repeated several times. 
 

 

When the pressure is correct and the heating system is drained from air, remove the 
filing hose. 

 

Connecting to heating network 

2.6.3

 

Open the valves 

Heating network media, supply

 and 

Heating network media, return. 

Start with supply then return. 
 

 

When all water connections are done and all circuits are pressurized, look for leaks. 
 

 

If connections need retightening after the installation has been taken into service, the 
system must be depressurised. If the system is not depressurised, gaskets will be 
damaged. 

 

Connecting the electrical equipment 

2.7

 

Remove the lid that covers the connection box and loosen the connection box from 
the insulation. 

 

Outdoor temperature sensor 

Room thermostat 

Supply temperature sensor 

Actuator, heating 

 

 

Install the room thermostat; se

2.11 Installing the room thermostat

. 

 

 

Connect the non-polarity cable, from room thermostat to the connection box. 
Carefully press the cable into the trail in the insulation. 

Summary of Contents for Mini City F2

Page 1: ...DOC 1380 2016 15 Installation and operating Alfa Laval Mini City EN NL SV FR...

Page 2: ......

Page 3: ...3 Alfa Laval Mini City Installation and operating 4 Installation och drift 14 Electrical connections 24 Packing list 25 Declaration of conformity 26 EN SV...

Page 4: ...g circuit 9 2 6 3 Connecting to heating network 9 Connecting the electrical equipment 9 2 7 Mounting options 10 2 8 Commissioning advice AL Mini City 10 2 9 General adjustments and settings 10 2 10 In...

Page 5: ...t very hot and should not be touched When starting up the substation To avoid the risk of scalding make sure that no one draws any hot water until the hot water temperature has been adjusted Start hea...

Page 6: ...15 Heating network media return 16 Cold water cw 17 Cold water outlet cw 18 Hot water hw 20 Heating circuit return 21 Heating circuit supply 22 Drain valve 24 Connection box for electric power and sen...

Page 7: ...ch as outer walls or on concrete walls Check the applicable regulations of the primary heating supplier The available differential pressure should be at least 50 kPa and at most 600 kPa Where the diff...

Page 8: ...e wall with four screws Mount the expansion vessel to the frame with the provided nut Mount the collection pipe assembly four parts Connect the collection pipe assembly to the expansion vessel and tig...

Page 9: ...rect and the heating system is drained from air remove the filing hose Connecting to heating network 2 6 3 Open the valves Heating network media supply and Heating network media return Start with supp...

Page 10: ...on see manual Installation Service And Operating Instruction AL Mini City on http www alfalaval com minicity Commissioning advice AL Mini City 2 9 Adjust the hot water temperature by having a hot wate...

Page 11: ...1 EN Installing the room thermostat 2 11 1 Removing power supply 2 Placement 3 Removing the dial 4 Removing the thermostat 5a Mounting direct on the wall 5b Mounting in wall socket 6 Connecting the ca...

Page 12: ...e room thermostat controls the supply temperature to the heating system The room thermostat is pre set to use control mode 2 Outside Temperature Control OTC control 1 Put the electrical cable from the...

Page 13: ...tion Require a connected outdoor temperature sensor Supply setpoint is based on the outside and room temperature 4 Constant supply temperature with Heat demand input Select a fixed supply temperature...

Page 14: ...fyllning och avluftning av v rme systemet 18 2 6 3 Anslutning till v rmen tverket 19 Anslutning av elektroniken 19 2 7 Monteringa av tillval 20 2 8 Drifts ttning AL Mini City 20 2 9 Allm nt 20 2 10 In...

Page 15: ...kan bli mycket varma och f r d rf r inte vidr ras Vid ig ngk rning av v rmecentralen f r att undvika sk llningsrisk se till att ingen anv nder tappvarmvatten innan varmvattentemperaturen har justerats...

Page 16: ...atten 14 V rmen tverk tillopp 15 V rmen tverk retur 16 Kallvatten 17 Kallvatten utlopp 18 Varmvatten 20 V rmekrets retur 21 V rmekrets tillopp 22 Avluftningsventil 24 Kopplingsbox f r el och givare v...

Page 17: ...kommenderar att v rmecentralen b r placeras p stabila isolerade v ggar s som ytterv ggar eller v ggar av betong Kontrollera g llande best mmelser fr n v rmeleverant ren Det tillg ngliga differenstryck...

Page 18: ...delar Anslut samlingsr ret till expansionsk rlet och dra med 30Nm Montera den korta slangen mellan expansionsk rlet och anslutningen efter pumpen Montera spillr ret till s kerhetsventilen p kallvatten...

Page 19: ...t r tagit i drift m ste systemet g ras tryckl st Annars kommer packningarna att skadas Anslutning av elektroniken 2 7 Tabort locket som t cker kopplingsboxen Lossa f rsiktigt kopplingsboxen fr n isole...

Page 20: ...temperaturen vid tappst llet med en termometer Stabiliseringstiden r cirka 20 sekunder Varmvattentemperaturen b r st llas till ca 50 C Alfa Laval rekommenderar att prim r tilloppstemperatur r minst 1...

Page 21: ...21 SV Installation av rumstermostaten 2 11 1 Removing power supply 2 Placering 3 Tabort vridreglaget 4 Tabort termostaten 5a Montering direkt p v gg 5b Montering i ett v gguttag 6 Anslutning av kabel...

Page 22: ...framledningstemperaturen till v rmesystemet Rumstermostaten f rinst lld p driftl ge 2 utomhuskompensering OTC kontroll 5 Anslut centralens elkontakt till ett v gguttag 6 Vi rekommenderar att det finns...

Page 23: ...fr n rumstemperatur b rv rdet och utetemperaturen 9 Konstant framledningstemperatur med v rmebehovs efterfr gan Anv nds med ett tv zons system eller med ett golvv rmesystem med flera zoner V lj ett fa...

Page 24: ...Alfa Laval Mini City Installation and operating 24 Electrical connections...

Page 25: ...utter 6 1 Hose Slang 7 1 Hose Slang 8 1 Plug Plugg 9 1 Power cable EU UK N tsp nnings sladd EU UK 10 1 Gasket Packning 11 1 Frame to expansion vessel Ram till expansions k rl 12 1 Expansion vessel Exp...

Page 26: ...Alfa Laval Mini City Installation and operating 26 Declaration of conformity...

Reviews: