CAUTION
Turning of the connections will damage the gaskets on the end plate and
cause leakage.
Fit the pipes so that no tension is transferred to the heat exhanger. Nozzle
loads are not permitted.
Pipes connected to the pressure plate and to the connection plates must allow
±1% of the distance from the connection to the frame plate (see the assembly
PHE drawing).
Connections in the pressure plate
It is important that the plate pack has been tightened to the correct dimension
A
(check against the PHE drawing) before the piping system is connected.
When opening the heat exchanger, the pressure plate must be moved. Do not
use fixed pipes or other parts like feet, fasteners etc. inside the shaded area.
NOTE
Dismantle pipes from the pressure plate and the connections plate(s) so
that the pressure plate and the connection plate(s) are free to move along
the carrying bar.
Applicable for 3A standards
Once the unit is in position and the feet have been properly adjusted, it is the
responsibility of the end user to seal around the feet with silicone or caulking
to fulfil 3A standard.
200000423-1-EN-GB
21
Installation 4
EN