Alfa Laval Micro
Installation and service instruction
40
Fault Codes on the CM737
9.1
If a spanner is visible on the display there is an on ongoing alarm. Press the Info-button to view the fault code.
Error source
Error code
No fault (power-up)
0
Supply water temperature sensor out of range
1
Outside air temperature sensor out of range
2
Case temperature out of range
3
Secondary pump or district heating supply
4
No OT communication
7
Fault code 0
This fault code can just be seen in the fault history, parameter settings category 5.
Fault code 1
Supply sensor failure
Cause
Measured supply water temperature lies below 0°C or above 100°C.
Actions
Respond with ‘invalid data’ when thermostat asks for supply temperature Turn the
pump off, and enter off mode.
Fault code 2
Outside sensor out of operating range. This fault code can only occur after the
measured outside temperature has been in range: -40°C to 60°C.
Cause
Measured outside temperature lies below -40°C or above 60°C
Actions
When the thermostat asks for the outside temperature the DHC will respond with
‘invalid data’.
After a reset this fault code will not occur again, until a valid temperature has been
measured, and then a non-valid temperature will be measured again.
Fault code 3
Housing sensor out of operating range
Cause
Measured environment temperature lies below 0°C or above 60°C
Actions
Turn the pump off, and enter off mode
Fault code 4
Secondary pump or district heating supply:
Cause
Cannot reach the set supply water temperature
Actions
Air in the pump, low temp/ not district heating supply
Fault code 7
No OT communication:
Cause
Thermostat
doesn’t communicate by OT for 60 seconds
Actions
10 seconds after occurring, the DHC assumes an on/off thermostat is controller.
CH bit is cleared = 0.
Requested supply set point is cleared.
Fault is only cleared after a power cycle, OT thermostat is connected or
communication is working again.
Summary of Contents for AquaMicro
Page 2: ......
Page 16: ...Alfa Laval Micro Installation and service instruction 16 Measure sketch 2 9...
Page 19: ...Alfa Laval Micro Installation and service instruction 19 Picture 12...
Page 45: ...Alfa Laval Micro Installation and service instruction 45 Micro STC and Micro STC2 Picture 36...
Page 60: ...Alfa Laval Micro Installation and service instruction 60 17 Declaration of conformity...