Alderon Industries VersAlarm I/O VLIO-0001 Quick Start Manual Download Page 1

VersAlarm

 I/O

Indoor/Outdoor Alarm Panel | Model: VLIO-0001

Safety Guidelines

Step 2: Installing Conduit / Fittings

Before proceeding with the installation or operation of this product, 

read all instructions thoroughly, as well as complying with all federal, 

state and local codes, regulations, and practices. This product must 

be  installed  by  qualified  personnel  familiar  with  all  applicable  local 

electrical and mechanical codes. Refer to the National Electrical Code 

(NFPA 70). Failure to properly install and test this product can result in 

personal injury or equipment malfunction.

WARNING

Step 1: Remove Bottom Cover

Q

SG

00

00

1_

Re

v0

4_

VL

IO

-0

00

1_

Ve

rs

Al

ar

m I

O | S

ep

te

m

be

r 1

9, 2

02

2 1

0:

41 A

M

Remove the bottom enclosure cover screw, slide directly downward 

(1A) and then pull directly away (1B).

Using the pre-marked center hole 

locations (2A), mark and drill out 

on the bottom of the enclosure. 

The size(s) will depend on desired 

conduit  fitting  (maximum  0.75″). 

Place the conduit fitting (2B) in 

the drilled out hole and make sure 

it’s secured. Then, install conduit 

(2C) into the fitting.

Note: Seal all conduits to prevent moisture and 

gases from entering the enclosure per local codes.

CAUTION:

 Nonmetallic enclosure does not provide 

proper grounding between conduit connections. Use 

grounding bushings and jumper wires.

Step 3: Mount Enclosure

Determine the mounting location 

for the VersAlarm™ I/O. Hold the 

alarm up to the desired mounting 

location, mark the drill hole 

locations. Once marked, drill pilot 

holes for screws (not included) 

and use wall mount anchors (not 

included) if necessary. Place 

enclosure in mounting location, 

adjust until the pilot holes are 

lined up with the enclosure and 

fasten screws to secure the alarm 

panel in place.

QUICK START GUIDE

2A

2B

2C

1A

1B

Step 4: Wiring

The diagram below shows the six terminals on the terminal block that 

consists of three pairs of connections.

  1) Install the sensor to terminals 1 and 2.

  2) Installing an auxiliary device to terminals 3 and 4 is optional.

  3) Install incoming power to terminals 5 and 6, line (L1) in terminal 5 

    and neutral (N) in terminal 6.

  4) NEVER leave ground wire exposed inside the panel, use provided 

    Wago connector for wire termination.

Installing Wire into Wago Connector:

  1) Lift tab(s) upward.

  2) Insert wire(s) into slot.

  3) Press tab(s) downward.

  4) Make sure wire(s) are secured.

POWER

SENSOR

AUX

1

2

3

4

5

6

TO OPEN

WAGO

TO CLOSE

WAGO