Office alarm test
Operational tests
............................................................................................................................................................................................................................................................
365-372-304R7.1
Issue 1, November 2007
5 - 7
........................................................................................................................................................................................................................
14
Press the ACO pushbutton on the SYSCTL.
Result:
Activated office alarm: CR visual.
The CR audible alarm should clear.
........................................................................................................................................................................................................................
15
Reseat the pair of function units.
........................................................................................................................................................................................................................
16
Turn on the breaker that was turned off in
.
Result:
After a few minutes, all alarm indications should clear.
........................................................................................................................................................................................................................
17
Disconnect the office alarm cable connected in
for the remainder of the test
procedures in this chapter.
........................................................................................................................................................................................................................
18
Select Configuration -> Alarms -> Alarm Configuration.
........................................................................................................................................................................................................................
19
Choose Power Alarm Level: Minor.
........................................................................................................................................................................................................................
20
Click OK.
Important!
Do
NOT
delete the cross-connect that was entered for this test.
........................................................................................................................................................................................................................
21
Check off the appropriate box in
Appendix E, “Installation checklist”
.
........................................................................................................................................................
E
N D
O
F
S
T E P S