Viewing Results
36
13 Viewing Results
Main Menu > View Results
When data is in Cellcorder temporary storage, the Status screens display the
total number of cells with data, overall voltage (OV), averages, min-max
values, and threshold violations (faults).
Figure 17. Status Displays
TIP
: To go back a screen, exit a function, or return to the Main Menu, press
Back, Cancel or Esc.
13.1 Overall Voltage (OV) Data
Main Menu > View Results
The Cellcorder adds the cell voltages in a string and calculates overall
voltage (OV). Press View Results to display the number of cells that contain
data and the calculated OV of those cells. You may also view OV using the
BAS program and print OV in reports. The OV value cannot be typed in.
13.2 Status Screen: Average
Main Menu > View Results|Avg|More
Press Avg to display the average cell voltage (Vc), cell resistance (Rc), and
intercell resistance (Ric). Press More to display more average Ric, specific
gravity (SG), and temperature values.
13.3 Status Screen: Min-Max
Main Menu > View Results|Min-Max|More
Press Min-Max to display minimum and maximum values for Vc, Rc and
Ric, and the associated cell numbers. Press More to display more min-max
Ric, SG, and temperature values.
13.4 Status Screen: Faults
Main Menu > View Results|Faults|Volts
or
Rc
or
More|S/G
or
Temp
or
Ric
To display values that exceed thresholds, press Faults, then the item for
which you want faults displayed: Volts, Rc (internal cell resistance), S/G,
temperature or Ric (intercell resistance). To retest a voltage or resistance
reading that violates thresholds, press Retest.