Installing Optional Sensors/Transducers
4200-088
12-4
Revision 1.03
Figure 37 - FCCP Sensor
12.3.
Ambient Temperature Sensor
Up to two ambient temperature sensors can be installed per string. If there is only one temperature
sensor is being installed then the cable assembly is part number 1102-186-12 for 12’ or 1102-186-50 for
50’. If there are two temperature sensors being installed then the cable assembly is part number 1102-
187-12 for 12’ or 1102-187-50 for 50’.
To connect the temperature sensor, simply connect the four pin connector directly into the TEMP
connection on UXSM or UXCM depending on which components are being used. Place the temperature
sensor in an area that will exhibit a true ambient temperature where the batteries are exposed to.
When batteries are installed within a cabinet, typical a sensor is installed inside the cabinet at the
bottom and the other is installed towards the top of the cabinet.
Figure 38 - Single Temperature Sensor 1102-186-XX
Figure 39 - Double Temperature Sensors 1102-187-XX