Assembly
ATTENTION
Counter-hold using a suitable tool (e.g. pipe wrench) during connection of the heat exchang-
ers in order to avoid damage.
Install pipes and connections in such a way that the heat exchangers remain freely accessible
for maintenance.
Maximum working pressure: 16 bar
Maximum hot water flow temperature: 120 °C
Valves and actuators must be installed professionally. Please note here whether a version with a 2-way or 3-way
valve is to be implemented.
For the electrical connection of the actuator, see the circuit diagram.
2-way valve and 3-way valve versions
3-way valve
2-way valve
5
5
Fig. 30 2-way valve and 3-way valve connection versions
1
PCW cooler
3
Valve
2
Valve actuator
4
Recirculation pump (on-site)
Counterflow principle for heat exchanger connection
6
7
8
9
8
9
6
7
9
8
7
6
7
6
9
8
Fig. 31
Counterflow principle for heat exchanger connection
6
Air inlet
8
Media inlet
7
Air outlet
9
Media outlet