OperatinG instructiOns

stYLe 9301 pOrtaBLe FLOW Meter

a.  GeneraL

The Akron Brass Style 9301 Portable Flow Meter is designed for testing nozzles. The unit operates with a self contained 12 VDC 

rechargeable sealed lead acid battery and includes a Console with Meter and a Body with adapters for the Flow and Pressure 

Sensors and necessary Wiring, all housed in a convenient Carrying Case.

The rechargeable sealed lead acid battery has an average life of 10-12 hours on a full charge. A 110 VAC and a 12 VDC charger are 

also included.

  

Note: A battery low on charge may result in erratic readings.  Therefore, it is recommended the battery be charged before it’s initial 

use and after each use.

B. 

set-up

Check the O-Rings in the Flow Sensor for proper lubrication. If needed, apply a light coating of grease (O-Ring Lube or silicone).

Insert the Flow Sensor into the Sensor Port and align the locator pin to the hole and push down to seat. Then slip the Retaining 

Ring over the Sensor Cable and thread it down until snug.

The other end of the Cable is split into 2 Weatherpack connectors. One connector attaches to the Flow Sensor and one to the 

Pressure Transducer. Connect the one end of the cable to the Control Unit using the Screw Ring Plug.

When testing a nozzle with a pumper, connect a hose off a male discharge to the swivel inlet of the Portable Flow Meter.  Run 

another hose between the unit and the nozzle.  Turbulance at the inlet of the Portable Flow Meter may effect the 

accuracy of the unit.  For best results the following guidelines should always be followed:

Do not use any reducing adapter immediately prior to the Flow Meter inlet.  If reduction is necessary a short section (minimum 6’) 

of 2 1⁄2” hose is recommended.  

Once the unit is assembled, flip up the red switch cover and turn the toggle switch on.

The Portable Flow Meter is preset at the factory and ready to operate. No calibration should be required. If the unit would need 

calibration refer to the Operating Instructions on the following pages. 

c. 

OperatinG instructiOns

CAUTION: - This 9301 Portable Flow Meter is intended for training and/or testing of fire ground procedures, not actual use during 

fire ground operations.

These instructions describe the features and operational steps for general service after the system is set up. The Meter consists of a 

LCD display screen and two operation buttons located directly beneath the display. 

121838

Summary of Contents for Style

Page 1: ...to the Flow Sensor and one to the Pressure Transducer Connect the one end of the cable to the Control Unit using the Screw Ring Plug When testing a nozzle with a pumper connect a hose off a male discharge to the swivel inlet of the Portable Flow Meter Run another hose between the unit and the nozzle Turbulance at the inlet of the Portable Flow Meter may effect the accuracy of the unit For best res...

Page 2: ...NH 101420 3 Swivel Plug 742023 4 Gasket 717043 5 Ball Bearings 39 6 Retaining Nut 115497 7 Flow Sensor 93000046 8 Pressure Transducer Guard 115499 9 Pressure Transducer 93000050 10 Screw 4 765029 11 Control Unit PSI GPM LPM kPa 93151000 12 12VDC Vehicle Power Adapter 707390 13 110 VAC Charger 707386 13 240 VAC Charger 707497 14 Cable for Battery Charger 707387 NO ITEM PART NO 15 Case Inserts 70742...

Page 3: ...IPPED 1 4 22 18 GA FORKTERM TYP 7 REDWIRE BLACKWIRE BATTERY 17 18 19 FLOWMETER STYLE 9301 20 21 27 22 23 24 25 29 28 26 ITEM DESCRIPTION QTY 1 PLASTIC ENCLOSURE 1 2 FACE PLATE 1 3 SCREW 4 4 NUT 4 5 MICRO SWITCH 1 6 TOGGLE GUARD 1 7 CONTROLLER FLOW METER GPM PSI LPM KPA 1 8 TERMINAL STRIP 1 9 12V BATTERY 1 10 REAR MOUNTING PLATE 1 11 JACK 1 12 PANEL PLUG 1 13 BUTTON HEAD CAP SCREW 2 14 SPLIT LOCK W...

Page 4: ...nu Pressure Menu Display Menu Valve Menu Root Menu To navigate through all menus the left button SELECT will highlight an individual line Once highlighted the right button ENTER will open the selected menu EXPLANATION OF INDIVIDUAL MENU SCREENS UNITS MENU Units Menu This Menu is used to select GPM or LPM Gallons or Liters and PSI or kPa Example WithFLOWhighlighted pressENTERtochoosebetweenGPMandLP...

Page 5: ...HTNESSor CONTRAST to the desired level Press the ENTER button to lock in the setting Sensors Part Number Description 9300 0046 Flow Meter Sensor 9300 0050 Pressure Sensor ISO 9001 REGISTERED COMPANY PHONE 330 264 5678 or 800 228 1161 I FAX 330 264 2944 or 800 531 7335 I akronbrass com WARRANTY AND DISCLAIMER We warrant Akron Brass products for a period of five 5 years after purchase against defect...