PROCool
Electronic Panel
AKO-17632, AKO-17633, AKO-17634, AKO-17635, AKO-17636, AKO-17637, AKO-17520, AKO-17521
Quick guide
Maintenance
Clean the surface of the unit with a soft cloth, water and detergent. Do not use abrasive
detergents, petrol, white spirits or solvents.
Precautions
Using the equipment without following the manufacturer's instructions may affect the
device's safety requirements. To ensure that the device operates correctly, only probes
supplied by AKO should be used.
Between -40 ºC and +20 ºC, if the NTC probe is extended up to 1,000 m with minimum
0.5 mm² wire, the maximum deviation will be 0.25 ºC (Wire for probe extension ref.
AKO-15586
)
IMPORTANT:
Ÿ
The function of the digital inputs depends on the configuration.
Ÿ
The recommended currents and powers are the maximum working currents
and powers.
Description
Key function
Pressing it for 5 seconds activates the Stand-By mode. Pressing it for 2 seconds the unit
returns to the normal mode. In Stand-by mode, the unit performs no action and the
display only shows the
m
indicator along with the temperature.
During configuration, it exits the parameter without saving changes, returns to
previous level, or exits programming.
One short press* shows the non-displayed probe reading (see
P8
parameter).
Pressing it for 5 seconds starts/stops the defrost.
During configuration, it allows you to scroll through the different levels, or when
setting a parameter, to change its value.
Pressing for 5 seconds accesses the
quick configuration
menu.
Pressing for 10 seconds accesses the
advanced configuration
menu.
During configuration, it allows you to scroll through the different levels, or when
setting a parameter, to change its value.
One short press* displays the current set point value (SP).
Pressing it for 5 seconds accesses change set point.
During configuration, it accesses the level shown on the display or, when setting a
parameter, it accepts the new value.
Messages
Quick configuration
The quick configuration menu allows the unit to be configured for the most common
applications. Press the
key for 5 seconds to access it.
SP: Set point
It sets the coldroom's working temperature
d0: Defrost frequency
Time that must elapse between the starting of each defrost.
d1: Maximum defrost duration
The defrost will end after this time has elapsed since it started.
F3: Fan status during defrost
It defines the status of the fans during defrost.
Ÿ
0=
Stopped
Ÿ
1=
Running
A1: Maximum alarm probe 1
Defines the temperature at which the maximum alarm will be triggered. Only affects probe 1.
A2: Minimum alarm probe 1
Defines the temperature at which the minimum alarm will be triggered. Only affects probe 1.
P26: Stoppage owing to pump down
It defines whether this function is active
Ÿ
0
= Without pump down
Ÿ
1
= With pump down
Stand-by active mode
Temperature
*Short press: Less than 5 seconds.
L5
Flashing 0:
Access code (Password) request
You must enter the access code configured on
L5
to execute the requested
function. See also parameter
P2
.
E1
/
E2
Probe 1 or 2 faulty (open circuit, crossover or temperature outside the
probe limits;
NTC
: -50 To 99 ºC).
dEF
Indicates a defrost is underway. When the defrost process has finished, the
message will continue to be displayed during the time defined in
parameter
d3
.
AH
Alternating with temperature:
Maximum temperature in control probe alarm. Temperature set in
A1
has
been reached.
AL
Alternating with temperature:
Minimum temperature in control probe alarm. Temperature set in
A2
has
been reached.
AE
Alternating with temperature:
External alarm activated (by digital input).
AES
Alternating with temperature:
Severe external alarm activated (by digital input).
Adt
Alternating with temperature:
Defrost alarm time-out. Displayed when a defrost ends after the maximum
time elapsed as defined in parameter
d1
.
PAb
Alternating with temperature:
Door open alarm. Shown if the door remains open longer than specified in
parameter
A12
.
Pd
Alternating with temperature:
The maximum pump down stop time has been exceeded (
P15
)
LP
Alternating with temperature:
The maximum pump down start-up time has been exceeded (
P14
).
ASC
It indicates that a component in the compressor's safety chain has
triggered (compressor motor guard, thermistors or high pressure
controller).
Display
Stand-by key
Menu key
Set Point key
Defrost key
Alarm active
Compressor active (If
P26
=1)
Condenser fans
active
Defrosting in progress
Evaporator fans active
Solenoid active
ESC
SET
1
1763H202 Ed.02
GB